⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)1 AWGDrop: 3.04V (2.54%)
Voltage at Load End117.1 VLoss: 2.93 V (234.8 W)
Power & Breaker (125%)9.6 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A37.63 V (31.36%)82.4 V62.07 V (51.73%)3010.5 WDrop/Amp High
12 AWG3.31 mm²20 A23.65 V (19.71%)96.4 V39.01 V (32.51%)1891.8 WDrop/Amp High
10 AWG5.26 mm²30 A14.88 V (12.4%)105.1 V24.55 V (20.46%)1190.5 WDrop/Amp High
8 AWG8.37 mm²50 A9.35 V (7.79%)110.6 V15.43 V (12.85%)748.1 WDrop/Amp High
6 AWG13.3 mm²65 A5.89 V (4.9%)114.1 V9.71 V (8.09%)470.8 WDrop/Amp High
4 AWG21.15 mm²85 A3.7 V (3.08%)116.3 V6.1 V (5.09%)296.1 W~ ≤5%
3 AWG26.67 mm²100 A2.93 V (2.45%)117.1 V4.84 V (4.03%)234.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.33 V (1.94%)117.7 V3.84 V (3.2%)186.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.85 V (1.54%)118.2 V3.04 V (2.54%)147.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.46 V (1.22%)118.5 V2.41 V (2.01%)117.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.16 V (0.97%)118.8 V1.91 V (1.6%)92.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.92 V (0.77%)119.1 V1.52 V (1.27%)73.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.73 V (0.61%)119.3 V1.2 V (1.0%)58.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.62 V (0.51%)119.4 V1.02 V (0.85%)49.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.51 V (0.43%)119.5 V0.85 V (0.71%)41.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.44 V (0.37%)119.6 V0.73 V (0.61%)35.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.39 V (0.32%)119.6 V0.64 V (0.53%)30.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.31 V (0.26%)119.7 V0.51 V (0.42%)24.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.26 V (0.21%)119.7 V0.42 V (0.35%)20.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.21 V (0.17%)119.8 V0.34 V (0.28%)16.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.15 V (0.13%)119.8 V0.25 V (0.21%)12.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 75 feet one-way at 120V (1-Phase), you need 3 AWG copper wire. This produces a voltage drop of 2.93V (2.45%) and delivers 117.1V at the load.

What size aluminum wire is required for 80 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 3.04V (2.54%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.