⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.05V (2.54%)
Voltage at Load End117.1 VLoss: 2.94 V (117.7 W)
Power & Breaker (125%)4.8 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A18.82 V (15.68%)101.2 V31.04 V (25.86%)752.6 WDrop/Amp High
12 AWG3.31 mm²20 A11.82 V (9.85%)108.2 V19.5 V (16.25%)472.9 WDrop/Amp High
10 AWG5.26 mm²30 A7.44 V (6.2%)112.6 V12.27 V (10.23%)297.6 WDrop/Amp High
8 AWG8.37 mm²50 A4.68 V (3.9%)115.3 V7.71 V (6.43%)187.0 W~ ≤5%
6 AWG13.3 mm²65 A2.94 V (2.45%)117.1 V4.85 V (4.04%)117.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.85 V (1.54%)118.1 V3.05 V (2.54%)74.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.47 V (1.22%)118.5 V2.42 V (2.02%)58.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.16 V (0.97%)118.8 V1.92 V (1.6%)46.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.92 V (0.77%)119.1 V1.52 V (1.27%)36.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.73 V (0.61%)119.3 V1.21 V (1.01%)29.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.58 V (0.48%)119.4 V0.96 V (0.8%)23.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.46 V (0.38%)119.5 V0.76 V (0.63%)18.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.37 V (0.3%)119.6 V0.6 V (0.5%)14.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.31 V (0.26%)119.7 V0.51 V (0.42%)12.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.26 V (0.21%)119.7 V0.42 V (0.35%)10.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (0.18%)119.8 V0.36 V (0.3%)8.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.19 V (0.16%)119.8 V0.32 V (0.27%)7.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (0.13%)119.8 V0.25 V (0.21%)6.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.11%)119.9 V0.21 V (0.18%)5.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.09%)119.9 V0.17 V (0.14%)4.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.06%)119.9 V0.13 V (0.11%)3.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 75 feet one-way at 120V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 2.94V (2.45%) and delivers 117.1V at the load.

What size aluminum wire is required for 40 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.05V (2.54%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.