⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 800 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.51V (4.25%)
Voltage at Load End11.7 VLoss: 0.31 V (4.6 W)
Power & Breaker (125%)0.18 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 800 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A75.26 V (627.18%)0.0 V124.15 V (1034.56%)1128.9 WDrop/Amp High
12 AWG3.31 mm²20 A47.29 V (394.12%)0.0 V78.01 V (650.12%)709.4 WDrop/Amp High
10 AWG5.26 mm²30 A29.76 V (248.01%)0.0 V49.09 V (409.1%)446.4 WDrop/Amp High
8 AWG8.37 mm²50 A18.7 V (155.86%)0.0 V30.85 V (257.1%)280.5 WDrop/Amp High
6 AWG13.3 mm²65 A11.77 V (98.09%)0.2 V19.42 V (161.8%)176.6 WDrop/Amp High
4 AWG21.15 mm²85 A7.4 V (61.68%)4.6 V12.21 V (101.74%)111.0 WDrop/Amp High
3 AWG26.67 mm²100 A5.87 V (48.91%)6.1 V9.68 V (80.69%)88.0 WDrop/Amp High
2 AWG33.62 mm²115 A4.66 V (38.8%)7.3 V7.68 V (64.01%)69.8 WDrop/Amp High
1 AWG42.41 mm²130 A3.69 V (30.76%)8.3 V6.09 V (50.74%)55.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.93 V (24.39%)9.1 V4.83 V (40.23%)43.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.32 V (19.35%)9.7 V3.83 V (31.91%)34.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.84 V (15.35%)10.2 V3.04 V (25.31%)27.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.46 V (12.17%)10.5 V2.41 V (20.07%)21.9 WDrop/Amp High
250 kcmil126.7 mm²255 A1.24 V (10.3%)10.8 V2.04 V (16.98%)18.5 WDrop/Amp High
300 kcmil152.0 mm²285 A1.03 V (8.58%)11.0 V1.7 V (14.16%)15.4 WDrop/Amp High
350 kcmil177.3 mm²310 A0.88 V (7.36%)11.1 V1.46 V (12.14%)13.2 WDrop/Amp High
400 kcmil202.7 mm²335 A0.77 V (6.44%)11.2 V1.27 V (10.62%)11.6 WDrop/Amp High
500 kcmil253.4 mm²380 A0.62 V (5.15%)11.4 V1.02 V (8.49%)9.3 WDrop/Amp High
600 kcmil304.0 mm²420 A0.51 V (4.29%)11.5 V0.85 V (7.08%)7.7 W~ ≤5%
750 kcmil380.0 mm²475 A0.41 V (3.43%)11.6 V0.68 V (5.66%)6.2 W~ ≤5%
1000 kcmil506.7 mm²545 A0.31 V (2.57%)11.7 V0.51 V (4.25%)4.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 800 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 800 feet one-way at 12V (DC), you need 1000 kcmil copper wire. This produces a voltage drop of 0.31V (2.57%) and delivers 11.7V at the load.

What size aluminum wire is required for 15 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.51V (4.25%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.