🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 150 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.66%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 3.19V (2.65%)
Voltage at Load End116.8 VLoss: 3.19 V (559.0 W)
Power & Breaker (125%)21.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 150 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A164.64 V (137.2%)0.0 V271.57 V (226.31%)28811.3 WDrop/Amp High
12 AWG3.31 mm²20 A103.46 V (86.21%)16.5 V170.66 V (142.21%)18105.0 WDrop/Amp High
10 AWG5.26 mm²30 A65.1 V (54.25%)54.9 V107.39 V (89.49%)11393.1 WDrop/Amp High
8 AWG8.37 mm²50 A40.91 V (34.09%)79.1 V67.49 V (56.24%)7159.8 WDrop/Amp High
6 AWG13.3 mm²65 A25.75 V (21.46%)94.3 V42.47 V (35.39%)4505.8 WDrop/Amp High
4 AWG21.15 mm²85 A16.19 V (13.49%)103.8 V26.71 V (22.26%)2833.5 WDrop/Amp High
3 AWG26.67 mm²100 A12.84 V (10.7%)107.2 V21.18 V (17.65%)2247.0 WDrop/Amp High
2 AWG33.62 mm²115 A10.19 V (8.49%)109.8 V16.8 V (14.0%)1782.5 WDrop/Amp High
1 AWG42.41 mm²130 A8.07 V (6.73%)111.9 V13.32 V (11.1%)1413.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.4 V (5.33%)113.6 V10.56 V (8.8%)1120.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.08 V (4.23%)114.9 V8.38 V (6.98%)888.7 W~ ≤5%
3/0 AWG85.01 mm²200 A4.03 V (3.36%)116.0 V6.64 V (5.54%)704.9 W~ ≤5%
4/0 AWG107.2 mm²230 A3.19 V (2.66%)116.8 V5.27 V (4.39%)559.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.7 V (2.25%)117.3 V4.46 V (3.72%)473.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.25 V (1.88%)117.7 V3.72 V (3.1%)394.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.93 V (1.61%)118.1 V3.19 V (2.65%)338.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.69 V (1.41%)118.3 V2.79 V (2.32%)295.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.35 V (1.13%)118.6 V2.23 V (1.86%)236.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.13 V (0.94%)118.9 V1.86 V (1.55%)197.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.9 V (0.75%)119.1 V1.49 V (1.24%)157.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.68 V (0.56%)119.3 V1.11 V (0.93%)118.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 150 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 150 feet one-way at 120V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 3.19V (2.66%) and delivers 116.8V at the load.

What size aluminum wire is required for 175 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 3.19V (2.65%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.