175 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.1V (2.58%)
Voltage at Load End116.6 VLoss: 3.36 V (587.5 W)
Power & Breaker (125%)21.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A137.2 V (114.33%)0.0 V226.31 V (188.59%)24009.4 WDrop/Amp High
12 AWG3.31 mm²20 A86.21 V (71.85%)33.8 V142.21 V (118.51%)15087.5 WDrop/Amp High
10 AWG5.26 mm²30 A54.25 V (45.21%)65.7 V89.49 V (74.58%)9494.2 WDrop/Amp High
8 AWG8.37 mm²50 A34.09 V (28.41%)85.9 V56.24 V (46.87%)5966.5 WDrop/Amp High
6 AWG13.3 mm²65 A21.46 V (17.88%)98.5 V35.39 V (29.49%)3754.9 WDrop/Amp High
4 AWG21.15 mm²85 A13.49 V (11.24%)106.5 V22.26 V (18.55%)2361.2 WDrop/Amp High
3 AWG26.67 mm²100 A10.7 V (8.92%)109.3 V17.65 V (14.71%)1872.5 WDrop/Amp High
2 AWG33.62 mm²115 A8.49 V (7.07%)111.5 V14.0 V (11.67%)1485.4 WDrop/Amp High
1 AWG42.41 mm²130 A6.73 V (5.61%)113.3 V11.1 V (9.25%)1177.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.33 V (4.45%)114.7 V8.8 V (7.33%)933.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.23 V (3.53%)115.8 V6.98 V (5.82%)740.6 W~ ≤5%
3/0 AWG85.01 mm²200 A3.36 V (2.8%)116.6 V5.54 V (4.61%)587.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.66 V (2.22%)117.3 V4.39 V (3.66%)465.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.25 V (1.88%)117.7 V3.72 V (3.1%)394.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.88 V (1.56%)118.1 V3.1 V (2.58%)328.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.61 V (1.34%)118.4 V2.65 V (2.21%)281.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.41 V (1.17%)118.6 V2.32 V (1.94%)246.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.13 V (0.94%)118.9 V1.86 V (1.55%)197.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.94 V (0.78%)119.1 V1.55 V (1.29%)164.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.75 V (0.63%)119.2 V1.24 V (1.03%)131.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.56 V (0.47%)119.4 V0.93 V (0.77%)98.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 125 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 3.36V (2.8%) and delivers 116.6V at the load.

What size aluminum wire is required for 175 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.1V (2.58%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.