🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 3.25V (2.71%)
Voltage at Load End116.8 VLoss: 3.15 V (551.8 W)
Power & Breaker (125%)21.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A192.08 V (160.06%)0.0 V316.83 V (264.03%)33613.2 WDrop/Amp High
12 AWG3.31 mm²20 A120.7 V (100.58%)0.0 V199.1 V (165.92%)21122.5 WDrop/Amp High
10 AWG5.26 mm²30 A75.95 V (63.29%)44.0 V125.29 V (104.41%)13291.9 WDrop/Amp High
8 AWG8.37 mm²50 A47.73 V (39.78%)72.3 V78.74 V (65.61%)8353.1 WDrop/Amp High
6 AWG13.3 mm²65 A30.04 V (25.03%)90.0 V49.55 V (41.29%)5256.8 WDrop/Amp High
4 AWG21.15 mm²85 A18.89 V (15.74%)101.1 V31.16 V (25.97%)3305.7 WDrop/Amp High
3 AWG26.67 mm²100 A14.98 V (12.48%)105.0 V24.71 V (20.59%)2621.5 WDrop/Amp High
2 AWG33.62 mm²115 A11.88 V (9.9%)108.1 V19.6 V (16.33%)2079.6 WDrop/Amp High
1 AWG42.41 mm²130 A9.42 V (7.85%)110.6 V15.54 V (12.95%)1648.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.47 V (6.22%)112.5 V12.32 V (10.27%)1307.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.92 V (4.94%)114.1 V9.77 V (8.14%)1036.9 W~ ≤5%
3/0 AWG85.01 mm²200 A4.7 V (3.92%)115.3 V7.75 V (6.46%)822.4 W~ ≤5%
4/0 AWG107.2 mm²230 A3.73 V (3.11%)116.3 V6.15 V (5.12%)652.2 W~ ≤5%
250 kcmil126.7 mm²255 A3.15 V (2.63%)116.8 V5.2 V (4.33%)551.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.63 V (2.19%)117.4 V4.34 V (3.61%)460.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.25 V (1.88%)117.7 V3.72 V (3.1%)394.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.97 V (1.64%)118.0 V3.25 V (2.71%)344.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.58 V (1.31%)118.4 V2.6 V (2.17%)275.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.31 V (1.1%)118.7 V2.17 V (1.81%)230.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.05 V (0.88%)118.9 V1.73 V (1.45%)184.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.79 V (0.66%)119.2 V1.3 V (1.08%)138.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 175 feet one-way at 120V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 3.15V (2.63%) and delivers 116.8V at the load.

What size aluminum wire is required for 175 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 3.25V (2.71%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.