175 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.19%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.3V (10.84%)
Voltage at Load End11.7 VLoss: 0.26 V (46.0 W)
Power & Breaker (125%)2.1 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A192.08 V (1600.63%)0.0 V316.83 V (2640.29%)33613.2 WDrop/Amp High
12 AWG3.31 mm²20 A120.7 V (1005.83%)0.0 V199.1 V (1659.15%)21122.5 WDrop/Amp High
10 AWG5.26 mm²30 A75.95 V (632.95%)0.0 V125.29 V (1044.07%)13291.9 WDrop/Amp High
8 AWG8.37 mm²50 A47.73 V (397.77%)0.0 V78.74 V (656.13%)8353.1 WDrop/Amp High
6 AWG13.3 mm²65 A30.04 V (250.32%)0.0 V49.55 V (412.92%)5256.8 WDrop/Amp High
4 AWG21.15 mm²85 A18.89 V (157.41%)0.0 V31.16 V (259.66%)3305.7 WDrop/Amp High
3 AWG26.67 mm²100 A14.98 V (124.83%)0.0 V24.71 V (205.92%)2621.5 WDrop/Amp High
2 AWG33.62 mm²115 A11.88 V (99.03%)0.1 V19.6 V (163.35%)2079.6 WDrop/Amp High
1 AWG42.41 mm²130 A9.42 V (78.5%)2.6 V15.54 V (129.49%)1648.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.47 V (62.24%)4.5 V12.32 V (102.67%)1307.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.92 V (49.37%)6.1 V9.77 V (81.44%)1036.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.7 V (39.16%)7.3 V7.75 V (64.6%)822.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.73 V (31.06%)8.3 V6.15 V (51.23%)652.2 WDrop/Amp High
250 kcmil126.7 mm²255 A3.15 V (26.28%)8.8 V5.2 V (43.34%)551.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.63 V (21.9%)9.4 V4.34 V (36.13%)460.0 WDrop/Amp High
350 kcmil177.3 mm²310 A2.25 V (18.78%)9.7 V3.72 V (30.97%)394.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.97 V (16.42%)10.0 V3.25 V (27.09%)344.9 WDrop/Amp High
500 kcmil253.4 mm²380 A1.58 V (13.14%)10.4 V2.6 V (21.67%)275.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.31 V (10.95%)10.7 V2.17 V (18.07%)230.0 WDrop/Amp High
750 kcmil380.0 mm²475 A1.05 V (8.76%)10.9 V1.73 V (14.45%)184.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.79 V (6.57%)11.2 V1.3 V (10.84%)138.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 175 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.26V (2.19%) and delivers 11.7V at the load.

What size aluminum wire is required for 175 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.3V (10.84%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.