🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 75 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 1.06%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 2.28V (1.1%)
Voltage at Load End205.8 VLoss: 2.2 V (666.6 W)
Power & Breaker (125%)63.05 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 75 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A71.29 V (34.27%)136.7 V117.59 V (56.54%)21608.5 WDrop/Amp High
12 AWG3.31 mm²20 A44.8 V (21.54%)163.2 V73.9 V (35.53%)13578.7 WDrop/Amp High
10 AWG5.26 mm²30 A28.19 V (13.55%)179.8 V46.5 V (22.36%)8544.8 WDrop/Amp High
8 AWG8.37 mm²50 A17.72 V (8.52%)190.3 V29.22 V (14.05%)5369.8 WDrop/Amp High
6 AWG13.3 mm²65 A11.15 V (5.36%)196.9 V18.39 V (8.84%)3379.4 WDrop/Amp High
4 AWG21.15 mm²85 A7.01 V (3.37%)201.0 V11.56 V (5.56%)2125.1 WDrop/Amp High
3 AWG26.67 mm²100 A5.56 V (2.67%)202.4 V9.17 V (4.41%)1685.2 WDrop/Amp High
2 AWG33.62 mm²115 A4.41 V (2.12%)203.6 V7.28 V (3.5%)1336.9 WDrop/Amp High
1 AWG42.41 mm²130 A3.5 V (1.68%)204.5 V5.77 V (2.77%)1059.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.77 V (1.33%)205.2 V4.57 V (2.2%)840.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.2 V (1.06%)205.8 V3.63 V (1.74%)666.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.74 V (0.84%)206.3 V2.88 V (1.38%)528.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.38 V (0.67%)206.6 V2.28 V (1.1%)419.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.17 V (0.56%)206.8 V1.93 V (0.93%)354.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.98 V (0.47%)207.0 V1.61 V (0.77%)295.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.84 V (0.4%)207.2 V1.38 V (0.66%)253.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.73 V (0.35%)207.3 V1.21 V (0.58%)221.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.59 V (0.28%)207.4 V0.97 V (0.46%)177.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.49 V (0.23%)207.5 V0.8 V (0.39%)147.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.39 V (0.19%)207.6 V0.64 V (0.31%)118.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.29 V (0.14%)207.7 V0.48 V (0.23%)88.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 75 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 75 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 2.2V (1.06%) and delivers 205.8V at the load.

What size aluminum wire is required for 175 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 2.28V (1.1%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.