⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 30 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 0.42%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 0.91V (0.44%)
Voltage at Load End207.1 VLoss: 0.88 V (266.6 W)
Power & Breaker (125%)63.05 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 30 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A28.52 V (13.71%)179.5 V47.04 V (22.61%)8643.4 WDrop/Amp High
12 AWG3.31 mm²20 A17.92 V (8.62%)190.1 V29.56 V (14.21%)5431.5 WDrop/Amp High
10 AWG5.26 mm²30 A11.28 V (5.42%)196.7 V18.6 V (8.94%)3417.9 WDrop/Amp High
8 AWG8.37 mm²50 A7.09 V (3.41%)200.9 V11.69 V (5.62%)2147.9 WDrop/Amp High
6 AWG13.3 mm²65 A4.46 V (2.14%)203.5 V7.36 V (3.54%)1351.7 WDrop/Amp High
4 AWG21.15 mm²85 A2.8 V (1.35%)205.2 V4.63 V (2.22%)850.0 WDrop/Amp High
3 AWG26.67 mm²100 A2.22 V (1.07%)205.8 V3.67 V (1.76%)674.1 WDrop/Amp High
2 AWG33.62 mm²115 A1.76 V (0.85%)206.2 V2.91 V (1.4%)534.7 WDrop/Amp High
1 AWG42.41 mm²130 A1.4 V (0.67%)206.6 V2.31 V (1.11%)423.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.11 V (0.53%)206.9 V1.83 V (0.88%)336.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.88 V (0.42%)207.1 V1.45 V (0.7%)266.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.7 V (0.34%)207.3 V1.15 V (0.55%)211.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.55 V (0.27%)207.4 V0.91 V (0.44%)167.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.47 V (0.23%)207.5 V0.77 V (0.37%)141.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.39 V (0.19%)207.6 V0.64 V (0.31%)118.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.33 V (0.16%)207.7 V0.55 V (0.27%)101.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.29 V (0.14%)207.7 V0.48 V (0.23%)88.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (0.11%)207.8 V0.39 V (0.19%)70.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.2 V (0.09%)207.8 V0.32 V (0.15%)59.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.16 V (0.08%)207.8 V0.26 V (0.12%)47.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.12 V (0.06%)207.9 V0.19 V (0.09%)35.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 30 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 30 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 0.88V (0.42%) and delivers 207.1V at the load.

What size aluminum wire is required for 175 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 0.91V (0.44%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.