175 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 1.76%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 3.8V (1.83%)
Voltage at Load End204.3 VLoss: 3.67 V (1110.9 W)
Power & Breaker (125%)63.05 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A118.82 V (57.12%)89.2 V195.99 V (94.23%)36014.1 WDrop/Amp High
12 AWG3.31 mm²20 A74.66 V (35.9%)133.3 V123.16 V (59.21%)22631.2 WDrop/Amp High
10 AWG5.26 mm²30 A46.98 V (22.59%)161.0 V77.5 V (37.26%)14241.3 WDrop/Amp High
8 AWG8.37 mm²50 A29.53 V (14.2%)178.5 V48.7 V (23.42%)8949.7 WDrop/Amp High
6 AWG13.3 mm²65 A18.58 V (8.93%)189.4 V30.65 V (14.74%)5632.3 WDrop/Amp High
4 AWG21.15 mm²85 A11.68 V (5.62%)196.3 V19.27 V (9.27%)3541.8 WDrop/Amp High
3 AWG26.67 mm²100 A9.27 V (4.46%)198.7 V15.29 V (7.35%)2808.7 WDrop/Amp High
2 AWG33.62 mm²115 A7.35 V (3.53%)200.6 V12.13 V (5.83%)2228.1 WDrop/Amp High
1 AWG42.41 mm²130 A5.83 V (2.8%)202.2 V9.61 V (4.62%)1766.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.62 V (2.22%)203.4 V7.62 V (3.66%)1400.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.67 V (1.76%)204.3 V6.05 V (2.91%)1110.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.91 V (1.4%)205.1 V4.8 V (2.31%)881.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.31 V (1.11%)205.7 V3.8 V (1.83%)698.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.95 V (0.94%)206.0 V3.22 V (1.55%)591.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.63 V (0.78%)206.4 V2.68 V (1.29%)492.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.39 V (0.67%)206.6 V2.3 V (1.11%)422.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.22 V (0.59%)206.8 V2.01 V (0.97%)369.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.98 V (0.47%)207.0 V1.61 V (0.77%)295.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.81 V (0.39%)207.2 V1.34 V (0.64%)246.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.65 V (0.31%)207.3 V1.07 V (0.52%)197.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.49 V (0.23%)207.5 V0.8 V (0.39%)147.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 125 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 3.67V (1.76%) and delivers 204.3V at the load.

What size aluminum wire is required for 175 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 3.8V (1.83%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.