🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 5.32V (2.56%)
Voltage at Load End202.9 VLoss: 5.13 V (1555.3 W)
Power & Breaker (125%)63.05 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A166.34 V (79.97%)41.7 V274.39 V (131.92%)50419.8 WDrop/Amp High
12 AWG3.31 mm²20 A104.53 V (50.25%)103.5 V172.42 V (82.9%)31683.7 WDrop/Amp High
10 AWG5.26 mm²30 A65.78 V (31.62%)142.2 V108.5 V (52.16%)19937.9 WDrop/Amp High
8 AWG8.37 mm²50 A41.34 V (19.87%)166.7 V68.19 V (32.78%)12529.6 WDrop/Amp High
6 AWG13.3 mm²65 A26.01 V (12.51%)182.0 V42.91 V (20.63%)7885.2 WDrop/Amp High
4 AWG21.15 mm²85 A16.36 V (7.86%)191.6 V26.98 V (12.97%)4958.5 WDrop/Amp High
3 AWG26.67 mm²100 A12.97 V (6.24%)195.0 V21.4 V (10.29%)3932.2 WDrop/Amp High
2 AWG33.62 mm²115 A10.29 V (4.95%)197.7 V16.98 V (8.16%)3119.4 WDrop/Amp High
1 AWG42.41 mm²130 A8.16 V (3.92%)199.8 V13.46 V (6.47%)2472.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.47 V (3.11%)201.5 V10.67 V (5.13%)1960.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.13 V (2.47%)202.9 V8.46 V (4.07%)1555.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.07 V (1.96%)203.9 V6.71 V (3.23%)1233.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.23 V (1.55%)204.8 V5.32 V (2.56%)978.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.73 V (1.31%)205.3 V4.5 V (2.17%)827.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.28 V (1.09%)205.7 V3.75 V (1.81%)690.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.95 V (0.94%)206.0 V3.22 V (1.55%)591.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.71 V (0.82%)206.3 V2.82 V (1.35%)517.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.37 V (0.66%)206.6 V2.25 V (1.08%)413.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.14 V (0.55%)206.9 V1.88 V (0.9%)345.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.91 V (0.44%)207.1 V1.5 V (0.72%)276.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.68 V (0.33%)207.3 V1.13 V (0.54%)207.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 175 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.13V (2.47%) and delivers 202.9V at the load.

What size aluminum wire is required for 175 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 5.32V (2.56%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.