🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.57V (2.32%)
Voltage at Load End233.2 VLoss: 6.76 V (1182.5 W)
Power & Breaker (125%)42.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A823.18 V (342.99%)0.0 V1357.86 V (565.78%)144056.5 WDrop/Amp High
12 AWG3.31 mm²20 A517.29 V (215.54%)0.0 V853.28 V (355.53%)90524.9 WDrop/Amp High
10 AWG5.26 mm²30 A325.52 V (135.63%)0.0 V536.95 V (223.73%)56965.3 WDrop/Amp High
8 AWG8.37 mm²50 A204.57 V (85.24%)35.4 V337.44 V (140.6%)35799.0 WDrop/Amp High
6 AWG13.3 mm²65 A128.74 V (53.64%)111.3 V212.36 V (88.48%)22529.1 WDrop/Amp High
4 AWG21.15 mm²85 A80.96 V (33.73%)159.0 V133.54 V (55.64%)14167.3 WDrop/Amp High
3 AWG26.67 mm²100 A64.2 V (26.75%)175.8 V105.9 V (44.12%)11235.0 WDrop/Amp High
2 AWG33.62 mm²115 A50.93 V (21.22%)189.1 V84.01 V (35.0%)8912.5 WDrop/Amp High
1 AWG42.41 mm²130 A40.37 V (16.82%)199.6 V66.6 V (27.75%)7065.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A32.01 V (13.34%)208.0 V52.8 V (22.0%)5601.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.39 V (10.58%)214.6 V41.89 V (17.45%)4443.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.14 V (8.39%)219.9 V33.22 V (13.84%)3524.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.97 V (6.66%)224.0 V26.35 V (10.98%)2795.1 WDrop/Amp High
250 kcmil126.7 mm²255 A13.51 V (5.63%)226.5 V22.29 V (9.29%)2364.9 WDrop/Amp High
300 kcmil152.0 mm²285 A11.26 V (4.69%)228.7 V18.58 V (7.74%)1971.3 W~ ≤5%
350 kcmil177.3 mm²310 A9.66 V (4.02%)230.3 V15.93 V (6.64%)1690.0 W~ ≤5%
400 kcmil202.7 mm²335 A8.45 V (3.52%)231.6 V13.93 V (5.81%)1478.2 W~ ≤5%
500 kcmil253.4 mm²380 A6.76 V (2.82%)233.2 V11.15 V (4.64%)1182.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.63 V (2.35%)234.4 V9.29 V (3.87%)985.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.51 V (1.88%)235.5 V7.43 V (3.1%)788.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.38 V (1.41%)236.6 V5.57 V (2.32%)591.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 750 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 6.76V (2.82%) and delivers 233.2V at the load.

What size aluminum wire is required for 175 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.57V (2.32%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.