🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.15V (2.56%)
Voltage at Load End234.1 VLoss: 5.92 V (1036.9 W)
Power & Breaker (125%)42.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A192.08 V (80.03%)47.9 V316.83 V (132.01%)33613.2 WDrop/Amp High
12 AWG3.31 mm²20 A120.7 V (50.29%)119.3 V199.1 V (82.96%)21122.5 WDrop/Amp High
10 AWG5.26 mm²30 A75.95 V (31.65%)164.0 V125.29 V (52.2%)13291.9 WDrop/Amp High
8 AWG8.37 mm²50 A47.73 V (19.89%)192.3 V78.74 V (32.81%)8353.1 WDrop/Amp High
6 AWG13.3 mm²65 A30.04 V (12.52%)210.0 V49.55 V (20.65%)5256.8 WDrop/Amp High
4 AWG21.15 mm²85 A18.89 V (7.87%)221.1 V31.16 V (12.98%)3305.7 WDrop/Amp High
3 AWG26.67 mm²100 A14.98 V (6.24%)225.0 V24.71 V (10.3%)2621.5 WDrop/Amp High
2 AWG33.62 mm²115 A11.88 V (4.95%)228.1 V19.6 V (8.17%)2079.6 WDrop/Amp High
1 AWG42.41 mm²130 A9.42 V (3.93%)230.6 V15.54 V (6.47%)1648.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.47 V (3.11%)232.5 V12.32 V (5.13%)1307.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.92 V (2.47%)234.1 V9.77 V (4.07%)1036.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.7 V (1.96%)235.3 V7.75 V (3.23%)822.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.73 V (1.55%)236.3 V6.15 V (2.56%)652.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.15 V (1.31%)236.8 V5.2 V (2.17%)551.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.63 V (1.1%)237.4 V4.34 V (1.81%)460.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.25 V (0.94%)237.7 V3.72 V (1.55%)394.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.97 V (0.82%)238.0 V3.25 V (1.35%)344.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.58 V (0.66%)238.4 V2.6 V (1.08%)275.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.31 V (0.55%)238.7 V2.17 V (0.9%)230.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.05 V (0.44%)238.9 V1.73 V (0.72%)184.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.79 V (0.33%)239.2 V1.3 V (0.54%)138.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 175 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.92V (2.47%) and delivers 234.1V at the load.

What size aluminum wire is required for 175 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.15V (2.56%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.