⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 1.69%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 4.22V (1.76%)
Voltage at Load End235.9 VLoss: 4.06 V (711.0 W)
Power & Breaker (125%)42.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A131.71 V (54.88%)108.3 V217.26 V (90.52%)23049.0 WDrop/Amp High
12 AWG3.31 mm²20 A82.77 V (34.49%)157.2 V136.52 V (56.89%)14484.0 WDrop/Amp High
10 AWG5.26 mm²30 A52.08 V (21.7%)187.9 V85.91 V (35.8%)9114.4 WDrop/Amp High
8 AWG8.37 mm²50 A32.73 V (13.64%)207.3 V53.99 V (22.5%)5727.8 WDrop/Amp High
6 AWG13.3 mm²65 A20.6 V (8.58%)219.4 V33.98 V (14.16%)3604.7 WDrop/Amp High
4 AWG21.15 mm²85 A12.95 V (5.4%)227.0 V21.37 V (8.9%)2266.8 WDrop/Amp High
3 AWG26.67 mm²100 A10.27 V (4.28%)229.7 V16.94 V (7.06%)1797.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.15 V (3.4%)231.9 V13.44 V (5.6%)1426.0 WDrop/Amp High
1 AWG42.41 mm²130 A6.46 V (2.69%)233.5 V10.66 V (4.44%)1130.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.12 V (2.13%)234.9 V8.45 V (3.52%)896.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.06 V (1.69%)235.9 V6.7 V (2.79%)711.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.22 V (1.34%)236.8 V5.32 V (2.21%)564.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.56 V (1.06%)237.4 V4.22 V (1.76%)447.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.16 V (0.9%)237.8 V3.57 V (1.49%)378.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.8 V (0.75%)238.2 V2.97 V (1.24%)315.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.55 V (0.64%)238.5 V2.55 V (1.06%)270.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.35 V (0.56%)238.6 V2.23 V (0.93%)236.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.08 V (0.45%)238.9 V1.78 V (0.74%)189.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.9 V (0.38%)239.1 V1.49 V (0.62%)157.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.72 V (0.3%)239.3 V1.19 V (0.5%)126.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.54 V (0.23%)239.5 V0.89 V (0.37%)94.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 120 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 4.06V (1.69%) and delivers 235.9V at the load.

What size aluminum wire is required for 175 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 4.22V (1.76%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.