⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.56V (2.97%)
Voltage at Load End116.6 VLoss: 3.43 V (68.7 W)
Power & Breaker (125%)2.4 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A21.95 V (18.29%)98.0 V36.21 V (30.17%)439.0 WDrop/Amp High
12 AWG3.31 mm²20 A13.79 V (11.5%)106.2 V22.75 V (18.96%)275.9 WDrop/Amp High
10 AWG5.26 mm²30 A8.68 V (7.23%)111.3 V14.32 V (11.93%)173.6 WDrop/Amp High
8 AWG8.37 mm²50 A5.46 V (4.55%)114.5 V9.0 V (7.5%)109.1 W~ ≤5%
6 AWG13.3 mm²65 A3.43 V (2.86%)116.6 V5.66 V (4.72%)68.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.16 V (1.8%)117.8 V3.56 V (2.97%)43.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.71 V (1.43%)118.3 V2.82 V (2.35%)34.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.36 V (1.13%)118.6 V2.24 V (1.87%)27.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.08 V (0.9%)118.9 V1.78 V (1.48%)21.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.85 V (0.71%)119.1 V1.41 V (1.17%)17.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.68 V (0.56%)119.3 V1.12 V (0.93%)13.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.54 V (0.45%)119.5 V0.89 V (0.74%)10.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.43 V (0.35%)119.6 V0.7 V (0.59%)8.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.36 V (0.3%)119.6 V0.59 V (0.5%)7.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.3 V (0.25%)119.7 V0.5 V (0.41%)6.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.26 V (0.21%)119.7 V0.42 V (0.35%)5.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (0.19%)119.8 V0.37 V (0.31%)4.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.18 V (0.15%)119.8 V0.3 V (0.25%)3.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.13%)119.8 V0.25 V (0.21%)3.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.1%)119.9 V0.2 V (0.17%)2.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.08%)119.9 V0.15 V (0.12%)1.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 175 feet one-way at 120V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 3.43V (2.86%) and delivers 116.6V at the load.

What size aluminum wire is required for 20 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.56V (2.97%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.