⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 1.38%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 7.35V (1.53%)
Voltage at Load End473.4 VLoss: 6.64 V (2301.9 W)
Power & Breaker (125%)166.28 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A271.58 V (56.58%)208.4 V447.98 V (93.33%)94077.7 WDrop/Amp High
12 AWG3.31 mm²20 A170.66 V (35.55%)309.3 V281.51 V (58.65%)59118.3 WDrop/Amp High
10 AWG5.26 mm²30 A107.39 V (22.37%)372.6 V177.15 V (36.91%)37201.8 WDrop/Amp High
8 AWG8.37 mm²50 A67.49 V (14.06%)412.5 V111.33 V (23.19%)23378.9 WDrop/Amp High
6 AWG13.3 mm²65 A42.47 V (8.85%)437.5 V70.06 V (14.6%)14712.9 WDrop/Amp High
4 AWG21.15 mm²85 A26.71 V (5.56%)453.3 V44.06 V (9.18%)9252.1 WDrop/Amp High
3 AWG26.67 mm²100 A21.18 V (4.41%)458.8 V34.94 V (7.28%)7337.1 WDrop/Amp High
2 AWG33.62 mm²115 A16.8 V (3.5%)463.2 V27.72 V (5.77%)5820.4 WDrop/Amp High
1 AWG42.41 mm²130 A13.32 V (2.77%)466.7 V21.97 V (4.58%)4614.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.56 V (2.2%)469.4 V17.42 V (3.63%)3658.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.38 V (1.75%)471.6 V13.82 V (2.88%)2902.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.64 V (1.38%)473.4 V10.96 V (2.28%)2301.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.27 V (1.1%)474.7 V8.69 V (1.81%)1825.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.46 V (0.93%)475.5 V7.35 V (1.53%)1544.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.72 V (0.77%)476.3 V6.13 V (1.28%)1287.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.19 V (0.66%)476.8 V5.26 V (1.09%)1103.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.79 V (0.58%)477.2 V4.6 V (0.96%)965.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.23 V (0.46%)477.8 V3.68 V (0.77%)772.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.86 V (0.39%)478.1 V3.07 V (0.64%)643.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.49 V (0.31%)478.5 V2.45 V (0.51%)515.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.11 V (0.23%)478.9 V1.84 V (0.38%)386.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 250 feet one-way at 480V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 6.64V (1.38%) and delivers 473.4V at the load.

What size aluminum wire is required for 200 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 7.35V (1.53%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.