⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 1.73%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 8.64V (1.8%)
Voltage at Load End471.7 VLoss: 8.32 V (1802.4 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A169.74 V (35.36%)310.3 V279.99 V (58.33%)36749.1 WDrop/Amp High
12 AWG3.31 mm²20 A106.66 V (22.22%)373.3 V175.94 V (36.65%)23093.1 WDrop/Amp High
10 AWG5.26 mm²30 A67.12 V (13.98%)412.9 V110.72 V (23.07%)14532.0 WDrop/Amp High
8 AWG8.37 mm²50 A42.18 V (8.79%)437.8 V69.58 V (14.5%)9132.4 WDrop/Amp High
6 AWG13.3 mm²65 A26.55 V (5.53%)453.5 V43.79 V (9.12%)5747.2 WDrop/Amp High
4 AWG21.15 mm²85 A16.69 V (3.48%)463.3 V27.54 V (5.74%)3614.1 WDrop/Amp High
3 AWG26.67 mm²100 A13.24 V (2.76%)466.8 V21.84 V (4.55%)2866.1 WDrop/Amp High
2 AWG33.62 mm²115 A10.5 V (2.19%)469.5 V17.32 V (3.61%)2273.6 WDrop/Amp High
1 AWG42.41 mm²130 A8.32 V (1.73%)471.7 V13.73 V (2.86%)1802.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A6.6 V (1.38%)473.4 V10.89 V (2.27%)1429.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A5.24 V (1.09%)474.8 V8.64 V (1.8%)1133.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.15 V (0.87%)475.8 V6.85 V (1.43%)899.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.29 V (0.69%)476.7 V5.43 V (1.13%)713.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.79 V (0.58%)477.2 V4.6 V (0.96%)603.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.32 V (0.48%)477.7 V3.83 V (0.8%)502.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.99 V (0.41%)478.0 V3.28 V (0.68%)431.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.74 V (0.36%)478.3 V2.87 V (0.6%)377.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.39 V (0.29%)478.6 V2.3 V (0.48%)301.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.16 V (0.24%)478.8 V1.92 V (0.4%)251.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.93 V (0.19%)479.1 V1.53 V (0.32%)201.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.7 V (0.15%)479.3 V1.15 V (0.24%)150.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 250 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 8.32V (1.73%) and delivers 471.7V at the load.

What size aluminum wire is required for 125 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 8.64V (1.8%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.