🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 40 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 1.02%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 1.36V (1.13%)
Voltage at Load End118.8 VLoss: 1.23 V (245.5 W)
Power & Breaker (125%)24.0 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 40 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A50.17 V (41.81%)69.8 V82.76 V (68.97%)10035.0 WDrop/Amp High
12 AWG3.31 mm²20 A31.53 V (26.27%)88.5 V52.01 V (43.34%)6306.0 WDrop/Amp High
10 AWG5.26 mm²30 A19.84 V (16.53%)100.2 V32.73 V (27.27%)3968.2 WDrop/Amp High
8 AWG8.37 mm²50 A12.47 V (10.39%)107.5 V20.57 V (17.14%)2493.8 WDrop/Amp High
6 AWG13.3 mm²65 A7.85 V (6.54%)112.2 V12.94 V (10.79%)1569.4 WDrop/Amp High
4 AWG21.15 mm²85 A4.93 V (4.11%)115.1 V8.14 V (6.78%)986.9 WDrop/Amp High
3 AWG26.67 mm²100 A3.91 V (3.26%)116.1 V6.45 V (5.38%)782.6 WDrop/Amp High
2 AWG33.62 mm²115 A3.1 V (2.59%)116.9 V5.12 V (4.27%)620.8 WDrop/Amp High
1 AWG42.41 mm²130 A2.46 V (2.05%)117.5 V4.06 V (3.38%)492.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.95 V (1.63%)118.0 V3.22 V (2.68%)390.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.55 V (1.29%)118.5 V2.55 V (2.13%)309.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.23 V (1.02%)118.8 V2.03 V (1.69%)245.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.97 V (0.81%)119.0 V1.61 V (1.34%)194.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.82 V (0.69%)119.2 V1.36 V (1.13%)164.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.69 V (0.57%)119.3 V1.13 V (0.94%)137.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.59 V (0.49%)119.4 V0.97 V (0.81%)117.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.51 V (0.43%)119.5 V0.85 V (0.71%)103.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.41 V (0.34%)119.6 V0.68 V (0.57%)82.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.34 V (0.29%)119.7 V0.57 V (0.47%)68.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.27 V (0.23%)119.7 V0.45 V (0.38%)54.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.17%)119.8 V0.34 V (0.28%)41.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 40 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 40 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 1.23V (1.02%) and delivers 118.8V at the load.

What size aluminum wire is required for 200 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 1.36V (1.13%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.