⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.05%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 2.72V (2.26%)
Voltage at Load End117.5 VLoss: 2.46 V (491.1 W)
Power & Breaker (125%)24.0 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 80 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A100.35 V (83.62%)19.7 V165.53 V (137.94%)20069.9 WDrop/Amp High
12 AWG3.31 mm²20 A63.06 V (52.55%)56.9 V104.02 V (86.68%)12611.9 WDrop/Amp High
10 AWG5.26 mm²30 A39.68 V (33.07%)80.3 V65.46 V (54.55%)7936.4 WDrop/Amp High
8 AWG8.37 mm²50 A24.94 V (20.78%)95.1 V41.14 V (34.28%)4987.5 WDrop/Amp High
6 AWG13.3 mm²65 A15.69 V (13.08%)104.3 V25.89 V (21.57%)3138.8 WDrop/Amp High
4 AWG21.15 mm²85 A9.87 V (8.22%)110.1 V16.28 V (13.57%)1973.8 WDrop/Amp High
3 AWG26.67 mm²100 A7.83 V (6.52%)112.2 V12.91 V (10.76%)1565.3 WDrop/Amp High
2 AWG33.62 mm²115 A6.21 V (5.17%)113.8 V10.24 V (8.53%)1241.7 WDrop/Amp High
1 AWG42.41 mm²130 A4.92 V (4.1%)115.1 V8.12 V (6.77%)984.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.9 V (3.25%)116.1 V6.44 V (5.36%)780.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.1 V (2.58%)116.9 V5.11 V (4.26%)619.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.46 V (2.05%)117.5 V4.05 V (3.38%)491.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.95 V (1.62%)118.1 V3.21 V (2.68%)389.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.65 V (1.37%)118.4 V2.72 V (2.26%)329.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.37 V (1.14%)118.6 V2.27 V (1.89%)274.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.18 V (0.98%)118.8 V1.94 V (1.62%)235.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.03 V (0.86%)119.0 V1.7 V (1.42%)205.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.82 V (0.69%)119.2 V1.36 V (1.13%)164.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.69 V (0.57%)119.3 V1.13 V (0.94%)137.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.55 V (0.46%)119.5 V0.91 V (0.76%)109.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.41 V (0.34%)119.6 V0.68 V (0.57%)82.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 80 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 80 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 2.46V (2.05%) and delivers 117.5V at the load.

What size aluminum wire is required for 200 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 2.72V (2.26%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.