⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 40 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.64%
Aluminum Wire (≤3% Drop)2 AWGDrop: 2.05V (1.71%)
Voltage at Load End118.0 VLoss: 1.97 V (157.9 W)
Power & Breaker (125%)9.6 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 40 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A20.07 V (16.72%)99.9 V33.11 V (27.59%)1605.6 WDrop/Amp High
12 AWG3.31 mm²20 A12.61 V (10.51%)107.4 V20.8 V (17.34%)1009.0 WDrop/Amp High
10 AWG5.26 mm²30 A7.94 V (6.61%)112.1 V13.09 V (10.91%)634.9 WDrop/Amp High
8 AWG8.37 mm²50 A4.99 V (4.16%)115.0 V8.23 V (6.86%)399.0 WDrop/Amp High
6 AWG13.3 mm²65 A3.14 V (2.62%)116.9 V5.18 V (4.31%)251.1 WDrop/Amp High
4 AWG21.15 mm²85 A1.97 V (1.64%)118.0 V3.26 V (2.71%)157.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.57 V (1.3%)118.4 V2.58 V (2.15%)125.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.24 V (1.03%)118.8 V2.05 V (1.71%)99.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.98 V (0.82%)119.0 V1.62 V (1.35%)78.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.78 V (0.65%)119.2 V1.29 V (1.07%)62.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.62 V (0.52%)119.4 V1.02 V (0.85%)49.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.49 V (0.41%)119.5 V0.81 V (0.68%)39.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.39 V (0.32%)119.6 V0.64 V (0.54%)31.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.33 V (0.27%)119.7 V0.54 V (0.45%)26.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (0.23%)119.7 V0.45 V (0.38%)22.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.24 V (0.2%)119.8 V0.39 V (0.32%)18.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.21 V (0.17%)119.8 V0.34 V (0.28%)16.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.14%)119.8 V0.27 V (0.23%)13.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.11%)119.9 V0.23 V (0.19%)11.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.09%)119.9 V0.18 V (0.15%)8.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.07%)119.9 V0.14 V (0.11%)6.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 40 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 40 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.97V (1.64%) and delivers 118.0V at the load.

What size aluminum wire is required for 80 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 2.05V (1.71%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.