⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 500 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 6.13V (2.95%)
Voltage at Load End202.4 VLoss: 5.57 V (1930.8 W)
Power & Breaker (125%)72.05 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 500 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A543.16 V (261.13%)0.0 V895.96 V (430.75%)188155.4 WDrop/Amp High
12 AWG3.31 mm²20 A341.32 V (164.1%)0.0 V563.02 V (270.68%)118236.6 WDrop/Amp High
10 AWG5.26 mm²30 A214.78 V (103.26%)0.0 V354.29 V (170.33%)74403.7 WDrop/Amp High
8 AWG8.37 mm²50 A134.98 V (64.89%)73.0 V222.65 V (107.04%)46757.8 WDrop/Amp High
6 AWG13.3 mm²65 A84.94 V (40.84%)123.1 V140.12 V (67.37%)29425.8 WDrop/Amp High
4 AWG21.15 mm²85 A53.42 V (25.68%)154.6 V88.11 V (42.36%)18504.2 WDrop/Amp High
3 AWG26.67 mm²100 A42.36 V (20.37%)165.6 V69.88 V (33.59%)14674.3 WDrop/Amp High
2 AWG33.62 mm²115 A33.6 V (16.16%)174.4 V55.43 V (26.65%)11640.8 WDrop/Amp High
1 AWG42.41 mm²130 A26.64 V (12.81%)181.4 V43.94 V (21.13%)9228.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.12 V (10.15%)186.9 V34.84 V (16.75%)7316.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.75 V (8.06%)191.2 V27.64 V (13.29%)5804.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.29 V (6.39%)194.7 V21.92 V (10.54%)4603.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.54 V (5.07%)197.5 V17.38 V (8.36%)3650.8 WDrop/Amp High
250 kcmil126.7 mm²255 A8.92 V (4.29%)199.1 V14.71 V (7.07%)3088.9 W~ ≤5%
300 kcmil152.0 mm²285 A7.43 V (3.57%)200.6 V12.26 V (5.89%)2574.8 W~ ≤5%
350 kcmil177.3 mm²310 A6.37 V (3.06%)201.6 V10.51 V (5.05%)2207.4 W~ ≤5%
400 kcmil202.7 mm²335 A5.57 V (2.68%)202.4 V9.19 V (4.42%)1930.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.46 V (2.14%)203.5 V7.35 V (3.54%)1544.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.72 V (1.79%)204.3 V6.13 V (2.95%)1287.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.97 V (1.43%)205.0 V4.9 V (2.36%)1029.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.23 V (1.07%)205.8 V3.68 V (1.77%)772.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 500 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 500 feet one-way at 208V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 5.57V (2.68%) and delivers 202.4V at the load.

What size aluminum wire is required for 200 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 6.13V (2.95%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.