🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 500 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.53%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.13V (2.95%)
Voltage at Load End202.7 VLoss: 5.27 V (912.7 W)
Power & Breaker (125%)36.03 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 500 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A271.58 V (130.57%)0.0 V447.98 V (215.37%)47038.8 WDrop/Amp High
12 AWG3.31 mm²20 A170.66 V (82.05%)37.3 V281.51 V (135.34%)29559.2 WDrop/Amp High
10 AWG5.26 mm²30 A107.39 V (51.63%)100.6 V177.15 V (85.17%)18600.9 WDrop/Amp High
8 AWG8.37 mm²50 A67.49 V (32.45%)140.5 V111.33 V (53.52%)11689.5 WDrop/Amp High
6 AWG13.3 mm²65 A42.47 V (20.42%)165.5 V70.06 V (33.68%)7356.5 WDrop/Amp High
4 AWG21.15 mm²85 A26.71 V (12.84%)181.3 V44.06 V (21.18%)4626.0 WDrop/Amp High
3 AWG26.67 mm²100 A21.18 V (10.18%)186.8 V34.94 V (16.8%)3668.6 WDrop/Amp High
2 AWG33.62 mm²115 A16.8 V (8.08%)191.2 V27.72 V (13.32%)2910.2 WDrop/Amp High
1 AWG42.41 mm²130 A13.32 V (6.4%)194.7 V21.97 V (10.56%)2307.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.56 V (5.08%)197.4 V17.42 V (8.37%)1829.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.38 V (4.03%)199.6 V13.82 V (6.64%)1451.0 W~ ≤5%
3/0 AWG85.01 mm²200 A6.64 V (3.19%)201.4 V10.96 V (5.27%)1150.9 W~ ≤5%
4/0 AWG107.2 mm²230 A5.27 V (2.53%)202.7 V8.69 V (4.18%)912.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.46 V (2.14%)203.5 V7.35 V (3.54%)772.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.72 V (1.79%)204.3 V6.13 V (2.95%)643.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.19 V (1.53%)204.8 V5.26 V (2.53%)551.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.79 V (1.34%)205.2 V4.6 V (2.21%)482.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.23 V (1.07%)205.8 V3.68 V (1.77%)386.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.86 V (0.89%)206.1 V3.07 V (1.47%)321.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.49 V (0.71%)206.5 V2.45 V (1.18%)257.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.11 V (0.54%)206.9 V1.84 V (0.88%)193.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 500 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 500 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.27V (2.53%) and delivers 202.7V at the load.

What size aluminum wire is required for 100 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.13V (2.95%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.