🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 500 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 5.75V (2.76%)
Voltage at Load End202.4 VLoss: 5.57 V (1206.6 W)
Power & Breaker (125%)45.03 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 500 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A339.47 V (163.21%)0.0 V559.97 V (269.22%)73498.2 WDrop/Amp High
12 AWG3.31 mm²20 A213.32 V (102.56%)0.0 V351.89 V (169.18%)46186.2 WDrop/Amp High
10 AWG5.26 mm²30 A134.24 V (64.54%)73.8 V221.43 V (106.46%)29063.9 WDrop/Amp High
8 AWG8.37 mm²50 A84.36 V (40.56%)123.6 V139.16 V (66.9%)18264.8 WDrop/Amp High
6 AWG13.3 mm²65 A53.09 V (25.52%)154.9 V87.57 V (42.1%)11494.5 WDrop/Amp High
4 AWG21.15 mm²85 A33.39 V (16.05%)174.6 V55.07 V (26.48%)7228.2 WDrop/Amp High
3 AWG26.67 mm²100 A26.48 V (12.73%)181.5 V43.67 V (21.0%)5732.1 WDrop/Amp High
2 AWG33.62 mm²115 A21.0 V (10.1%)187.0 V34.64 V (16.66%)4547.2 WDrop/Amp High
1 AWG42.41 mm²130 A16.65 V (8.0%)191.4 V27.46 V (13.2%)3604.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.2 V (6.35%)194.8 V21.77 V (10.47%)2858.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.47 V (5.03%)197.5 V17.27 V (8.3%)2267.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.31 V (3.99%)199.7 V13.7 V (6.59%)1798.3 W~ ≤5%
4/0 AWG107.2 mm²230 A6.59 V (3.17%)201.4 V10.87 V (5.22%)1426.1 W~ ≤5%
250 kcmil126.7 mm²255 A5.57 V (2.68%)202.4 V9.19 V (4.42%)1206.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.65 V (2.23%)203.4 V7.66 V (3.68%)1005.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.98 V (1.91%)204.0 V6.57 V (3.16%)862.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.48 V (1.67%)204.5 V5.75 V (2.76%)754.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.79 V (1.34%)205.2 V4.6 V (2.21%)603.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.32 V (1.12%)205.7 V3.83 V (1.84%)502.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.86 V (0.89%)206.1 V3.07 V (1.47%)402.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.39 V (0.67%)206.6 V2.3 V (1.11%)301.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 500 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 500 feet one-way at 208V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 5.57V (2.68%) and delivers 202.4V at the load.

What size aluminum wire is required for 125 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 5.75V (2.76%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.