🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.24%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 5.94V (2.48%)
Voltage at Load End234.6 VLoss: 5.37 V (1074.2 W)
Power & Breaker (125%)48.0 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A219.51 V (91.46%)20.5 V362.1 V (150.87%)43902.9 WDrop/Amp High
12 AWG3.31 mm²20 A137.94 V (57.48%)102.1 V227.54 V (94.81%)27588.5 WDrop/Amp High
10 AWG5.26 mm²30 A86.8 V (36.17%)153.2 V143.19 V (59.66%)17360.9 WDrop/Amp High
8 AWG8.37 mm²50 A54.55 V (22.73%)185.4 V89.98 V (37.49%)10910.2 WDrop/Amp High
6 AWG13.3 mm²65 A34.33 V (14.3%)205.7 V56.63 V (23.6%)6866.0 WDrop/Amp High
4 AWG21.15 mm²85 A21.59 V (9.0%)218.4 V35.61 V (14.84%)4317.6 WDrop/Amp High
3 AWG26.67 mm²100 A17.12 V (7.13%)222.9 V28.24 V (11.77%)3424.0 WDrop/Amp High
2 AWG33.62 mm²115 A13.58 V (5.66%)226.4 V22.4 V (9.33%)2716.2 WDrop/Amp High
1 AWG42.41 mm²130 A10.77 V (4.49%)229.2 V17.76 V (7.4%)2153.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.54 V (3.56%)231.5 V14.08 V (5.87%)1707.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.77 V (2.82%)233.2 V11.17 V (4.65%)1354.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.37 V (2.24%)234.6 V8.86 V (3.69%)1074.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.26 V (1.77%)235.7 V7.03 V (2.93%)851.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.6 V (1.5%)236.4 V5.94 V (2.48%)720.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.0 V (1.25%)237.0 V4.96 V (2.06%)600.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.58 V (1.07%)237.4 V4.25 V (1.77%)515.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.25 V (0.94%)237.7 V3.72 V (1.55%)450.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.8 V (0.75%)238.2 V2.97 V (1.24%)360.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.5 V (0.63%)238.5 V2.48 V (1.03%)300.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.2 V (0.5%)238.8 V1.98 V (0.83%)240.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.9 V (0.38%)239.1 V1.49 V (0.62%)180.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 175 feet one-way at 240V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 5.37V (2.24%) and delivers 234.6V at the load.

What size aluminum wire is required for 200 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 5.94V (2.48%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.