🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 0.51%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 1.36V (0.57%)
Voltage at Load End238.8 VLoss: 1.23 V (245.5 W)
Power & Breaker (125%)48.0 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A50.17 V (20.91%)189.8 V82.76 V (34.49%)10035.0 WDrop/Amp High
12 AWG3.31 mm²20 A31.53 V (13.14%)208.5 V52.01 V (21.67%)6306.0 WDrop/Amp High
10 AWG5.26 mm²30 A19.84 V (8.27%)220.2 V32.73 V (13.64%)3968.2 WDrop/Amp High
8 AWG8.37 mm²50 A12.47 V (5.2%)227.5 V20.57 V (8.57%)2493.8 WDrop/Amp High
6 AWG13.3 mm²65 A7.85 V (3.27%)232.2 V12.94 V (5.39%)1569.4 WDrop/Amp High
4 AWG21.15 mm²85 A4.93 V (2.06%)235.1 V8.14 V (3.39%)986.9 WDrop/Amp High
3 AWG26.67 mm²100 A3.91 V (1.63%)236.1 V6.45 V (2.69%)782.6 WDrop/Amp High
2 AWG33.62 mm²115 A3.1 V (1.29%)236.9 V5.12 V (2.13%)620.8 WDrop/Amp High
1 AWG42.41 mm²130 A2.46 V (1.03%)237.5 V4.06 V (1.69%)492.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.95 V (0.81%)238.0 V3.22 V (1.34%)390.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.55 V (0.64%)238.5 V2.55 V (1.06%)309.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.23 V (0.51%)238.8 V2.03 V (0.84%)245.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.97 V (0.41%)239.0 V1.61 V (0.67%)194.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.82 V (0.34%)239.2 V1.36 V (0.57%)164.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.69 V (0.29%)239.3 V1.13 V (0.47%)137.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.59 V (0.25%)239.4 V0.97 V (0.4%)117.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.51 V (0.21%)239.5 V0.85 V (0.35%)103.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.41 V (0.17%)239.6 V0.68 V (0.28%)82.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.34 V (0.14%)239.7 V0.57 V (0.24%)68.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.27 V (0.11%)239.7 V0.45 V (0.19%)54.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.09%)239.8 V0.34 V (0.14%)41.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 40 feet one-way at 240V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 1.23V (0.51%) and delivers 238.8V at the load.

What size aluminum wire is required for 200 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 1.36V (0.57%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.