⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 13.79V (2.87%)
Voltage at Load End466.6 VLoss: 13.38 V (4633.3 W)
Power & Breaker (125%)166.28 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A814.74 V (169.74%)0.0 V1343.93 V (279.99%)282233.1 WDrop/Amp High
12 AWG3.31 mm²20 A511.98 V (106.66%)0.0 V844.53 V (175.94%)177354.9 WDrop/Amp High
10 AWG5.26 mm²30 A322.18 V (67.12%)157.8 V531.44 V (110.72%)111605.5 WDrop/Amp High
8 AWG8.37 mm²50 A202.47 V (42.18%)277.5 V333.98 V (69.58%)70136.8 WDrop/Amp High
6 AWG13.3 mm²65 A127.42 V (26.55%)352.6 V210.18 V (43.79%)44138.7 WDrop/Amp High
4 AWG21.15 mm²85 A80.13 V (16.69%)399.9 V132.17 V (27.54%)27756.3 WDrop/Amp High
3 AWG26.67 mm²100 A63.54 V (13.24%)416.5 V104.81 V (21.84%)22011.4 WDrop/Amp High
2 AWG33.62 mm²115 A50.41 V (10.5%)429.6 V83.15 V (17.32%)17461.2 WDrop/Amp High
1 AWG42.41 mm²130 A39.96 V (8.32%)440.0 V65.91 V (13.73%)13842.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.68 V (6.6%)448.3 V52.26 V (10.89%)10974.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.13 V (5.24%)454.9 V41.46 V (8.64%)8706.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.93 V (4.15%)460.1 V32.88 V (6.85%)6905.6 W~ ≤5%
4/0 AWG107.2 mm²230 A15.81 V (3.29%)464.2 V26.08 V (5.43%)5476.2 W~ ≤5%
250 kcmil126.7 mm²255 A13.38 V (2.79%)466.6 V22.06 V (4.6%)4633.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A11.15 V (2.32%)468.9 V18.39 V (3.83%)3862.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A9.56 V (1.99%)470.4 V15.77 V (3.28%)3311.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A8.36 V (1.74%)471.6 V13.79 V (2.87%)2896.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A6.69 V (1.39%)473.3 V11.03 V (2.3%)2316.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.57 V (1.16%)474.4 V9.2 V (1.92%)1931.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.46 V (0.93%)475.5 V7.36 V (1.53%)1544.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.34 V (0.7%)476.7 V5.52 V (1.15%)1158.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 750 feet one-way at 480V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 13.38V (2.79%) and delivers 466.6V at the load.

What size aluminum wire is required for 200 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 13.79V (2.87%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.