🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 13.79V (2.87%)
Voltage at Load End468.1 VLoss: 11.86 V (3080.3 W)
Power & Breaker (125%)124.71 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A611.05 V (127.3%)0.0 V1007.95 V (209.99%)158756.1 WDrop/Amp High
12 AWG3.31 mm²20 A383.98 V (80.0%)96.0 V633.4 V (131.96%)99762.1 WDrop/Amp High
10 AWG5.26 mm²30 A241.63 V (50.34%)238.4 V398.58 V (83.04%)62778.1 WDrop/Amp High
8 AWG8.37 mm²50 A151.85 V (31.64%)328.1 V250.48 V (52.18%)39451.9 WDrop/Amp High
6 AWG13.3 mm²65 A95.56 V (19.91%)384.4 V157.63 V (32.84%)24828.0 WDrop/Amp High
4 AWG21.15 mm²85 A60.09 V (12.52%)419.9 V99.13 V (20.65%)15612.9 WDrop/Amp High
3 AWG26.67 mm²100 A47.66 V (9.93%)432.3 V78.61 V (16.38%)12381.4 WDrop/Amp High
2 AWG33.62 mm²115 A37.8 V (7.88%)442.2 V62.36 V (12.99%)9821.9 WDrop/Amp High
1 AWG42.41 mm²130 A29.97 V (6.24%)450.0 V49.44 V (10.3%)7786.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A23.76 V (4.95%)456.2 V39.19 V (8.17%)6173.4 W~ ≤5%
2/0 AWG67.43 mm²175 A18.85 V (3.93%)461.2 V31.09 V (6.48%)4897.1 W~ ≤5%
3/0 AWG85.01 mm²200 A14.95 V (3.11%)465.0 V24.66 V (5.14%)3884.4 W~ ≤5%
4/0 AWG107.2 mm²230 A11.86 V (2.47%)468.1 V19.56 V (4.07%)3080.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A10.03 V (2.09%)470.0 V16.55 V (3.45%)2606.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A8.36 V (1.74%)471.6 V13.79 V (2.87%)2172.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A7.17 V (1.49%)472.8 V11.82 V (2.46%)1862.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A6.27 V (1.31%)473.7 V10.34 V (2.15%)1629.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.02 V (1.04%)475.0 V8.27 V (1.72%)1303.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.18 V (0.87%)475.8 V6.9 V (1.44%)1086.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.34 V (0.7%)476.7 V5.52 V (1.15%)869.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.51 V (0.52%)477.5 V4.14 V (0.86%)651.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 750 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 11.86V (2.47%) and delivers 468.1V at the load.

What size aluminum wire is required for 150 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 13.79V (2.87%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.