🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.6%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 13.79V (2.87%)
Voltage at Load End467.5 VLoss: 12.46 V (2697.5 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A509.21 V (106.09%)0.0 V839.96 V (174.99%)110247.3 WDrop/Amp High
12 AWG3.31 mm²20 A319.99 V (66.66%)160.0 V527.83 V (109.96%)69279.3 WDrop/Amp High
10 AWG5.26 mm²30 A201.36 V (41.95%)278.6 V332.15 V (69.2%)43595.9 WDrop/Amp High
8 AWG8.37 mm²50 A126.54 V (26.36%)353.5 V208.74 V (43.49%)27397.2 WDrop/Amp High
6 AWG13.3 mm²65 A79.64 V (16.59%)400.4 V131.36 V (27.37%)17241.7 WDrop/Amp High
4 AWG21.15 mm²85 A50.08 V (10.43%)429.9 V82.61 V (17.21%)10842.3 WDrop/Amp High
3 AWG26.67 mm²100 A39.71 V (8.27%)440.3 V65.51 V (13.65%)8598.2 WDrop/Amp High
2 AWG33.62 mm²115 A31.5 V (6.56%)448.5 V51.97 V (10.83%)6820.8 WDrop/Amp High
1 AWG42.41 mm²130 A24.97 V (5.2%)455.0 V41.2 V (8.58%)5407.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.8 V (4.13%)460.2 V32.66 V (6.8%)4287.1 W~ ≤5%
2/0 AWG67.43 mm²175 A15.71 V (3.27%)464.3 V25.91 V (5.4%)3400.8 W~ ≤5%
3/0 AWG85.01 mm²200 A12.46 V (2.6%)467.5 V20.55 V (4.28%)2697.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A9.88 V (2.06%)470.1 V16.3 V (3.4%)2139.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A8.36 V (1.74%)471.6 V13.79 V (2.87%)1809.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A6.97 V (1.45%)473.0 V11.49 V (2.39%)1508.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.97 V (1.24%)474.0 V9.85 V (2.05%)1293.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.23 V (1.09%)474.8 V8.62 V (1.8%)1131.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.18 V (0.87%)475.8 V6.89 V (1.44%)905.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.48 V (0.73%)476.5 V5.75 V (1.2%)754.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.79 V (0.58%)477.2 V4.6 V (0.96%)603.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.09 V (0.44%)477.9 V3.45 V (0.72%)452.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 750 feet one-way at 480V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 12.46V (2.6%) and delivers 467.5V at the load.

What size aluminum wire is required for 125 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 13.79V (2.87%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.