200 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 800 ft (243.8 m) one-way run.
Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.88V (2.83%)
Voltage at Load End202.1 VLoss: 5.95 V (2059.8 W)
Power & Breaker (125%)72.05 kW250A Breaker Recommended
All AWG & kcmil Wire Gauges for 200 Amps at 800 Feet (208V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 869.05 V (417.81%) | 0.0 V | 1433.53 V (689.2%) | 301048.6 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 546.11 V (262.55%) | 0.0 V | 900.83 V (433.09%) | 189178.6 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 343.66 V (165.22%) | 0.0 V | 566.87 V (272.53%) | 119045.8 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 215.97 V (103.83%) | 0.0 V | 356.24 V (171.27%) | 74812.6 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 135.91 V (65.34%) | 72.1 V | 224.19 V (107.78%) | 47081.3 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 85.47 V (41.09%) | 122.5 V | 140.98 V (67.78%) | 29606.7 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 67.78 V (32.59%) | 140.2 V | 111.8 V (53.75%) | 23478.9 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 53.77 V (25.85%) | 154.2 V | 88.69 V (42.64%) | 18625.3 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 42.62 V (20.49%) | 165.4 V | 70.31 V (33.8%) | 14764.9 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 33.79 V (16.25%) | 174.2 V | 55.74 V (26.8%) | 11706.5 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 26.81 V (12.89%) | 181.2 V | 44.22 V (21.26%) | 9286.4 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 21.26 V (10.22%) | 186.7 V | 35.08 V (16.86%) | 7366.0 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 16.86 V (8.11%) | 191.1 V | 27.81 V (13.37%) | 5841.2 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 14.27 V (6.86%) | 193.7 V | 23.53 V (11.31%) | 4942.2 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 11.89 V (5.72%) | 196.1 V | 19.62 V (9.43%) | 4119.6 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 10.2 V (4.9%) | 197.8 V | 16.82 V (8.09%) | 3531.8 W | ~ ≤5% |
| 400 kcmil | 202.7 mm² | 335 A | 8.92 V (4.29%) | 199.1 V | 14.71 V (7.07%) | 3089.2 W | ~ ≤5% |
| 500 kcmil | 253.4 mm² | 380 A | 7.13 V (3.43%) | 200.9 V | 11.77 V (5.66%) | 2471.1 W | ~ ≤5% |
| 600 kcmil | 304.0 mm² | 420 A | 5.95 V (2.86%) | 202.1 V | 9.81 V (4.72%) | 2059.8 W | ✓ PASS (≤3%) |
| 750 kcmil | 380.0 mm² | 475 A | 4.76 V (2.29%) | 203.2 V | 7.85 V (3.77%) | 1647.8 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 3.57 V (1.72%) | 204.4 V | 5.88 V (2.83%) | 1235.8 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 200 amps at 800 feet (208V)?
To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 800 feet one-way at 208V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 5.95V (2.86%) and delivers 202.1V at the load.
What size aluminum wire is required for 200 amps at 800 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.88V (2.83%).
What breaker size is needed for a 200A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.