⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.58%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 5.56V (2.67%)
Voltage at Load End202.6 VLoss: 5.36 V (371.5 W)
Power & Breaker (125%)14.41 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A173.81 V (83.56%)34.2 V286.71 V (137.84%)12041.9 WDrop/Amp High
12 AWG3.31 mm²20 A109.22 V (52.51%)98.8 V180.17 V (86.62%)7567.1 WDrop/Amp High
10 AWG5.26 mm²30 A68.73 V (33.04%)139.3 V113.37 V (54.51%)4761.8 WDrop/Amp High
8 AWG8.37 mm²50 A43.19 V (20.77%)164.8 V71.25 V (34.25%)2992.5 WDrop/Amp High
6 AWG13.3 mm²65 A27.18 V (13.07%)180.8 V44.84 V (21.56%)1883.3 WDrop/Amp High
4 AWG21.15 mm²85 A17.09 V (8.22%)190.9 V28.2 V (13.56%)1184.3 WDrop/Amp High
3 AWG26.67 mm²100 A13.56 V (6.52%)194.4 V22.36 V (10.75%)939.2 WDrop/Amp High
2 AWG33.62 mm²115 A10.75 V (5.17%)197.2 V17.74 V (8.53%)745.0 WDrop/Amp High
1 AWG42.41 mm²130 A8.52 V (4.1%)199.5 V14.06 V (6.76%)590.6 W~ ≤5%
1/0 AWG53.49 mm²150 A6.76 V (3.25%)201.2 V11.15 V (5.36%)468.3 W~ ≤5%
2/0 AWG67.43 mm²175 A5.36 V (2.58%)202.6 V8.84 V (4.25%)371.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.25 V (2.04%)203.7 V7.02 V (3.37%)294.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.37 V (1.62%)204.6 V5.56 V (2.67%)233.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.85 V (1.37%)205.1 V4.71 V (2.26%)197.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.38 V (1.14%)205.6 V3.92 V (1.89%)164.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.04 V (0.98%)206.0 V3.36 V (1.62%)141.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.78 V (0.86%)206.2 V2.94 V (1.41%)123.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.43 V (0.69%)206.6 V2.35 V (1.13%)98.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.19 V (0.57%)206.8 V1.96 V (0.94%)82.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.95 V (0.46%)207.0 V1.57 V (0.75%)65.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.71 V (0.34%)207.3 V1.18 V (0.57%)49.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 800 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.36V (2.58%) and delivers 202.6V at the load.

What size aluminum wire is required for 40 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 5.56V (2.67%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.