🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 300 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.87V (23.89%)
Voltage at Load End11.7 VLoss: 0.35 V (78.2 W)
Power & Breaker (125%)2.7 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 300 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A423.35 V (3527.91%)0.0 V698.33 V (5819.41%)95253.7 WDrop/Amp High
12 AWG3.31 mm²20 A266.03 V (2216.94%)0.0 V438.83 V (3656.91%)59857.3 WDrop/Amp High
10 AWG5.26 mm²30 A167.41 V (1395.07%)0.0 V276.15 V (2301.21%)37666.8 WDrop/Amp High
8 AWG8.37 mm²50 A105.21 V (876.71%)0.0 V173.54 V (1446.16%)23671.2 WDrop/Amp High
6 AWG13.3 mm²65 A66.21 V (551.73%)0.0 V109.21 V (910.1%)14896.8 WDrop/Amp High
4 AWG21.15 mm²85 A41.63 V (346.95%)0.0 V68.68 V (572.31%)9367.7 WDrop/Amp High
3 AWG26.67 mm²100 A33.02 V (275.14%)0.0 V54.46 V (453.86%)7428.9 WDrop/Amp High
2 AWG33.62 mm²115 A26.19 V (218.26%)0.0 V43.2 V (360.03%)5893.1 WDrop/Amp High
1 AWG42.41 mm²130 A20.76 V (173.03%)0.0 V34.25 V (285.41%)4671.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.46 V (137.19%)0.0 V27.16 V (226.29%)3704.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.06 V (108.82%)0.0 V21.54 V (179.51%)2938.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.36 V (86.32%)1.6 V17.09 V (142.39%)2330.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.21 V (68.45%)3.8 V13.55 V (112.91%)1848.2 WDrop/Amp High
250 kcmil126.7 mm²255 A6.95 V (57.92%)5.0 V11.46 V (95.54%)1563.8 WDrop/Amp High
300 kcmil152.0 mm²285 A5.79 V (48.28%)6.2 V9.56 V (79.63%)1303.5 WDrop/Amp High
350 kcmil177.3 mm²310 A4.97 V (41.39%)7.0 V8.19 V (68.27%)1117.5 WDrop/Amp High
400 kcmil202.7 mm²335 A4.34 V (36.2%)7.7 V7.17 V (59.72%)977.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.48 V (28.96%)8.5 V5.73 V (47.77%)781.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.9 V (24.14%)9.1 V4.78 V (39.82%)651.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.32 V (19.31%)9.7 V3.82 V (31.85%)521.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.74 V (14.48%)10.3 V2.87 V (23.89%)391.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 300 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 300 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.9%) and delivers 11.7V at the load.

What size aluminum wire is required for 225 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.87V (23.89%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.