⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.67V (13.94%)
Voltage at Load End11.7 VLoss: 0.34 V (76.0 W)
Power & Breaker (125%)2.7 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A246.95 V (2057.95%)0.0 V407.36 V (3394.66%)55564.6 WDrop/Amp High
12 AWG3.31 mm²20 A155.19 V (1293.21%)0.0 V255.98 V (2133.2%)34916.8 WDrop/Amp High
10 AWG5.26 mm²30 A97.65 V (813.79%)0.0 V161.08 V (1342.37%)21972.3 WDrop/Amp High
8 AWG8.37 mm²50 A61.37 V (511.41%)0.0 V101.23 V (843.59%)13808.2 WDrop/Amp High
6 AWG13.3 mm²65 A38.62 V (321.84%)0.0 V63.71 V (530.89%)8689.8 WDrop/Amp High
4 AWG21.15 mm²85 A24.29 V (202.39%)0.0 V40.06 V (333.85%)5464.5 WDrop/Amp High
3 AWG26.67 mm²100 A19.26 V (160.5%)0.0 V31.77 V (264.75%)4333.5 WDrop/Amp High
2 AWG33.62 mm²115 A15.28 V (127.32%)0.0 V25.2 V (210.02%)3437.7 WDrop/Amp High
1 AWG42.41 mm²130 A12.11 V (100.93%)0.0 V19.98 V (166.49%)2725.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.6 V (80.02%)2.4 V15.84 V (132.0%)2160.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.62 V (63.48%)4.4 V12.57 V (104.71%)1714.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.04 V (50.35%)6.0 V9.97 V (83.06%)1359.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.79 V (39.93%)7.2 V7.9 V (65.87%)1078.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.05 V (33.78%)7.9 V6.69 V (55.73%)912.2 WDrop/Amp High
300 kcmil152.0 mm²285 A3.38 V (28.16%)8.6 V5.57 V (46.45%)760.4 WDrop/Amp High
350 kcmil177.3 mm²310 A2.9 V (24.14%)9.1 V4.78 V (39.82%)651.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.53 V (21.12%)9.5 V4.18 V (34.83%)570.2 WDrop/Amp High
500 kcmil253.4 mm²380 A2.03 V (16.89%)10.0 V3.34 V (27.86%)456.1 WDrop/Amp High
600 kcmil304.0 mm²420 A1.69 V (14.08%)10.3 V2.79 V (23.23%)380.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.35 V (11.26%)10.6 V2.23 V (18.58%)304.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.01 V (8.45%)11.0 V1.67 V (13.94%)228.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 175 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 225 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.67V (13.94%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.