🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.29V (2.39%)
Voltage at Load End11.7 VLoss: 0.35 V (78.2 W)
Power & Breaker (125%)2.7 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A42.33 V (352.79%)0.0 V69.83 V (581.94%)9525.4 WDrop/Amp High
12 AWG3.31 mm²20 A26.6 V (221.69%)0.0 V43.88 V (365.69%)5985.7 WDrop/Amp High
10 AWG5.26 mm²30 A16.74 V (139.51%)0.0 V27.61 V (230.12%)3766.7 WDrop/Amp High
8 AWG8.37 mm²50 A10.52 V (87.67%)1.5 V17.35 V (144.62%)2367.1 WDrop/Amp High
6 AWG13.3 mm²65 A6.62 V (55.17%)5.4 V10.92 V (91.01%)1489.7 WDrop/Amp High
4 AWG21.15 mm²85 A4.16 V (34.7%)7.8 V6.87 V (57.23%)936.8 WDrop/Amp High
3 AWG26.67 mm²100 A3.3 V (27.51%)8.7 V5.45 V (45.39%)742.9 WDrop/Amp High
2 AWG33.62 mm²115 A2.62 V (21.83%)9.4 V4.32 V (36.0%)589.3 WDrop/Amp High
1 AWG42.41 mm²130 A2.08 V (17.3%)9.9 V3.42 V (28.54%)467.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.65 V (13.72%)10.4 V2.72 V (22.63%)370.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.31 V (10.88%)10.7 V2.15 V (17.95%)293.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.04 V (8.63%)11.0 V1.71 V (14.24%)233.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.82 V (6.85%)11.2 V1.35 V (11.29%)184.8 WDrop/Amp High
250 kcmil126.7 mm²255 A0.7 V (5.79%)11.3 V1.15 V (9.55%)156.4 WDrop/Amp High
300 kcmil152.0 mm²285 A0.58 V (4.83%)11.4 V0.96 V (7.96%)130.3 W~ ≤5%
350 kcmil177.3 mm²310 A0.5 V (4.14%)11.5 V0.82 V (6.83%)111.7 W~ ≤5%
400 kcmil202.7 mm²335 A0.43 V (3.62%)11.6 V0.72 V (5.97%)97.7 W~ ≤5%
500 kcmil253.4 mm²380 A0.35 V (2.9%)11.7 V0.57 V (4.78%)78.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.29 V (2.41%)11.7 V0.48 V (3.98%)65.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.23 V (1.93%)11.8 V0.38 V (3.19%)52.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (1.45%)11.8 V0.29 V (2.39%)39.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 30 feet one-way at 12V (DC), you need 500 kcmil copper wire. This produces a voltage drop of 0.35V (2.9%) and delivers 11.7V at the load.

What size aluminum wire is required for 225 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.29V (2.39%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.