🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 75 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.72V (5.97%)
Voltage at Load End11.8 VLoss: 0.21 V (48.9 W)
Power & Breaker (125%)2.7 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 75 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A105.84 V (881.98%)0.0 V174.58 V (1454.85%)23813.4 WDrop/Amp High
12 AWG3.31 mm²20 A66.51 V (554.23%)0.0 V109.71 V (914.23%)14964.3 WDrop/Amp High
10 AWG5.26 mm²30 A41.85 V (348.77%)0.0 V69.04 V (575.3%)9416.7 WDrop/Amp High
8 AWG8.37 mm²50 A26.3 V (219.18%)0.0 V43.38 V (361.54%)5917.8 WDrop/Amp High
6 AWG13.3 mm²65 A16.55 V (137.93%)0.0 V27.3 V (227.53%)3724.2 WDrop/Amp High
4 AWG21.15 mm²85 A10.41 V (86.74%)1.6 V17.17 V (143.08%)2341.9 WDrop/Amp High
3 AWG26.67 mm²100 A8.25 V (68.79%)3.7 V13.62 V (113.46%)1857.2 WDrop/Amp High
2 AWG33.62 mm²115 A6.55 V (54.57%)5.5 V10.8 V (90.01%)1473.3 WDrop/Amp High
1 AWG42.41 mm²130 A5.19 V (43.26%)6.8 V8.56 V (71.35%)1167.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.12 V (34.3%)7.9 V6.79 V (56.57%)926.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.26 V (27.21%)8.7 V5.39 V (44.88%)734.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.59 V (21.58%)9.4 V4.27 V (35.6%)582.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.05 V (17.11%)9.9 V3.39 V (28.23%)462.1 WDrop/Amp High
250 kcmil126.7 mm²255 A1.74 V (14.48%)10.3 V2.87 V (23.88%)390.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.45 V (12.07%)10.6 V2.39 V (19.91%)325.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.24 V (10.35%)10.8 V2.05 V (17.07%)279.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.09 V (9.05%)10.9 V1.79 V (14.93%)244.4 WDrop/Amp High
500 kcmil253.4 mm²380 A0.87 V (7.24%)11.1 V1.43 V (11.94%)195.5 WDrop/Amp High
600 kcmil304.0 mm²420 A0.72 V (6.03%)11.3 V1.19 V (9.95%)162.9 WDrop/Amp High
750 kcmil380.0 mm²475 A0.58 V (4.83%)11.4 V0.96 V (7.96%)130.3 W~ ≤5%
1000 kcmil506.7 mm²545 A0.43 V (3.62%)11.6 V0.72 V (5.97%)97.8 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 75 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 75 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.21V (1.81%) and delivers 11.8V at the load.

What size aluminum wire is required for 225 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.72V (5.97%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.