⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 40 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.91%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 1.27V (1.06%)
Voltage at Load End118.9 VLoss: 1.1 V (246.4 W)
Power & Breaker (125%)27.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 40 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A56.45 V (47.04%)63.6 V93.11 V (77.59%)12700.5 WDrop/Amp High
12 AWG3.31 mm²20 A35.47 V (29.56%)84.5 V58.51 V (48.76%)7981.0 WDrop/Amp High
10 AWG5.26 mm²30 A22.32 V (18.6%)97.7 V36.82 V (30.68%)5022.2 WDrop/Amp High
8 AWG8.37 mm²50 A14.03 V (11.69%)106.0 V23.14 V (19.28%)3156.2 WDrop/Amp High
6 AWG13.3 mm²65 A8.83 V (7.36%)111.2 V14.56 V (12.13%)1986.2 WDrop/Amp High
4 AWG21.15 mm²85 A5.55 V (4.63%)114.4 V9.16 V (7.63%)1249.0 WDrop/Amp High
3 AWG26.67 mm²100 A4.4 V (3.67%)115.6 V7.26 V (6.05%)990.5 WDrop/Amp High
2 AWG33.62 mm²115 A3.49 V (2.91%)116.5 V5.76 V (4.8%)785.8 WDrop/Amp High
1 AWG42.41 mm²130 A2.77 V (2.31%)117.2 V4.57 V (3.81%)622.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.19 V (1.83%)117.8 V3.62 V (3.02%)493.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.74 V (1.45%)118.3 V2.87 V (2.39%)391.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.38 V (1.15%)118.6 V2.28 V (1.9%)310.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.1 V (0.91%)118.9 V1.81 V (1.51%)246.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.93 V (0.77%)119.1 V1.53 V (1.27%)208.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.77 V (0.64%)119.2 V1.27 V (1.06%)173.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.66 V (0.55%)119.3 V1.09 V (0.91%)149.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.58 V (0.48%)119.4 V0.96 V (0.8%)130.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.46 V (0.39%)119.5 V0.76 V (0.64%)104.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.39 V (0.32%)119.6 V0.64 V (0.53%)86.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.31 V (0.26%)119.7 V0.51 V (0.42%)69.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.19%)119.8 V0.38 V (0.32%)52.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 40 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 40 feet one-way at 120V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 1.1V (0.91%) and delivers 118.9V at the load.

What size aluminum wire is required for 225 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 1.27V (1.06%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.