🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 1.71%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 2.39V (1.99%)
Voltage at Load End117.9 VLoss: 2.05 V (462.1 W)
Power & Breaker (125%)27.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A105.84 V (88.2%)14.2 V174.58 V (145.49%)23813.4 WDrop/Amp High
12 AWG3.31 mm²20 A66.51 V (55.42%)53.5 V109.71 V (91.42%)14964.3 WDrop/Amp High
10 AWG5.26 mm²30 A41.85 V (34.88%)78.1 V69.04 V (57.53%)9416.7 WDrop/Amp High
8 AWG8.37 mm²50 A26.3 V (21.92%)93.7 V43.38 V (36.15%)5917.8 WDrop/Amp High
6 AWG13.3 mm²65 A16.55 V (13.79%)103.4 V27.3 V (22.75%)3724.2 WDrop/Amp High
4 AWG21.15 mm²85 A10.41 V (8.67%)109.6 V17.17 V (14.31%)2341.9 WDrop/Amp High
3 AWG26.67 mm²100 A8.25 V (6.88%)111.7 V13.62 V (11.35%)1857.2 WDrop/Amp High
2 AWG33.62 mm²115 A6.55 V (5.46%)113.5 V10.8 V (9.0%)1473.3 WDrop/Amp High
1 AWG42.41 mm²130 A5.19 V (4.33%)114.8 V8.56 V (7.14%)1167.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.12 V (3.43%)115.9 V6.79 V (5.66%)926.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.26 V (2.72%)116.7 V5.39 V (4.49%)734.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.59 V (2.16%)117.4 V4.27 V (3.56%)582.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.05 V (1.71%)117.9 V3.39 V (2.82%)462.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.74 V (1.45%)118.3 V2.87 V (2.39%)390.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.45 V (1.21%)118.6 V2.39 V (1.99%)325.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.24 V (1.03%)118.8 V2.05 V (1.71%)279.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.09 V (0.91%)118.9 V1.79 V (1.49%)244.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.87 V (0.72%)119.1 V1.43 V (1.19%)195.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.72 V (0.6%)119.3 V1.19 V (1.0%)162.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.58 V (0.48%)119.4 V0.96 V (0.8%)130.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.43 V (0.36%)119.6 V0.72 V (0.6%)97.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 75 feet one-way at 120V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 2.05V (1.71%) and delivers 117.9V at the load.

What size aluminum wire is required for 225 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 2.39V (1.99%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.