🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 450 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.3V (3.58%)
Voltage at Load End116.5 VLoss: 3.48 V (782.1 W)
Power & Breaker (125%)27.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 450 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A635.02 V (529.19%)0.0 V1047.49 V (872.91%)142880.5 WDrop/Amp High
12 AWG3.31 mm²20 A399.05 V (332.54%)0.0 V658.24 V (548.54%)89785.9 WDrop/Amp High
10 AWG5.26 mm²30 A251.11 V (209.26%)0.0 V414.22 V (345.18%)56500.3 WDrop/Amp High
8 AWG8.37 mm²50 A157.81 V (131.51%)0.0 V260.31 V (216.92%)35506.7 WDrop/Amp High
6 AWG13.3 mm²65 A99.31 V (82.76%)20.7 V163.82 V (136.52%)22345.2 WDrop/Amp High
4 AWG21.15 mm²85 A62.45 V (52.04%)57.5 V103.02 V (85.85%)14051.6 WDrop/Amp High
3 AWG26.67 mm²100 A49.53 V (41.27%)70.5 V81.69 V (68.08%)11143.3 WDrop/Amp High
2 AWG33.62 mm²115 A39.29 V (32.74%)80.7 V64.81 V (54.01%)8839.7 WDrop/Amp High
1 AWG42.41 mm²130 A31.14 V (25.95%)88.9 V51.37 V (42.81%)7007.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.69 V (20.58%)95.3 V40.73 V (33.94%)5556.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.59 V (16.32%)100.4 V32.31 V (26.93%)4407.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.54 V (12.95%)104.5 V25.63 V (21.36%)3496.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.32 V (10.27%)107.7 V20.32 V (16.94%)2772.3 WDrop/Amp High
250 kcmil126.7 mm²255 A10.43 V (8.69%)109.6 V17.2 V (14.33%)2345.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.69 V (7.24%)111.3 V14.33 V (11.95%)1955.2 WDrop/Amp High
350 kcmil177.3 mm²310 A7.45 V (6.21%)112.6 V12.29 V (10.24%)1676.2 WDrop/Amp High
400 kcmil202.7 mm²335 A6.52 V (5.43%)113.5 V10.75 V (8.96%)1466.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.21 V (4.34%)114.8 V8.6 V (7.17%)1172.8 W~ ≤5%
600 kcmil304.0 mm²420 A4.34 V (3.62%)115.7 V7.17 V (5.97%)977.6 W~ ≤5%
750 kcmil380.0 mm²475 A3.48 V (2.9%)116.5 V5.73 V (4.78%)782.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.61 V (2.17%)117.4 V4.3 V (3.58%)586.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 450 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 450 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.48V (2.9%) and delivers 116.5V at the load.

What size aluminum wire is required for 225 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.3V (3.58%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.