🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 1.12%
Aluminum Wire (≤3% Drop)10 AWGDrop: 8.86V (1.85%)
Voltage at Load End474.6 VLoss: 5.37 V (232.5 W)
Power & Breaker (125%)20.78 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A13.58 V (2.83%)466.4 V22.4 V (4.67%)588.0 WDrop/Amp High
12 AWG3.31 mm²20 A8.53 V (1.78%)471.5 V14.08 V (2.93%)369.5 WDrop/Amp High
10 AWG5.26 mm²30 A5.37 V (1.12%)474.6 V8.86 V (1.85%)232.5 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A3.37 V (0.7%)476.6 V5.57 V (1.16%)146.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.12 V (0.44%)477.9 V3.5 V (0.73%)92.0 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.34 V (0.28%)478.7 V2.2 V (0.46%)57.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.06 V (0.22%)478.9 V1.75 V (0.36%)45.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.84 V (0.18%)479.2 V1.39 V (0.29%)36.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.67 V (0.14%)479.3 V1.1 V (0.23%)28.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.53 V (0.11%)479.5 V0.87 V (0.18%)22.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.42 V (0.09%)479.6 V0.69 V (0.14%)18.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.33 V (0.07%)479.7 V0.55 V (0.11%)14.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.26 V (0.05%)479.7 V0.43 V (0.09%)11.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.22 V (0.05%)479.8 V0.37 V (0.08%)9.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.19 V (0.04%)479.8 V0.31 V (0.06%)8.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.16 V (0.03%)479.8 V0.26 V (0.05%)6.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (0.03%)479.9 V0.23 V (0.05%)6.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.11 V (0.02%)479.9 V0.18 V (0.04%)4.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.02%)479.9 V0.15 V (0.03%)4.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.02%)479.9 V0.12 V (0.03%)3.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.01%)479.9 V0.09 V (0.02%)2.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 100 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 5.37V (1.12%) and delivers 474.6V at the load.

What size aluminum wire is required for 25 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 8.86V (1.85%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.