🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.89%
Aluminum Wire (≤3% Drop)2 AWGDrop: 4.43V (0.92%)
Voltage at Load End475.7 VLoss: 4.27 V (592.1 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A43.45 V (9.05%)436.5 V71.68 V (14.93%)6021.0 WDrop/Amp High
12 AWG3.31 mm²20 A27.31 V (5.69%)452.7 V45.04 V (9.38%)3783.6 WDrop/Amp High
10 AWG5.26 mm²30 A17.18 V (3.58%)462.8 V28.34 V (5.9%)2380.9 WDrop/Amp High
8 AWG8.37 mm²50 A10.8 V (2.25%)469.2 V17.81 V (3.71%)1496.3 WDrop/Amp High
6 AWG13.3 mm²65 A6.8 V (1.42%)473.2 V11.21 V (2.34%)941.6 WDrop/Amp High
4 AWG21.15 mm²85 A4.27 V (0.89%)475.7 V7.05 V (1.47%)592.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.39 V (0.71%)476.6 V5.59 V (1.16%)469.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.69 V (0.56%)477.3 V4.43 V (0.92%)372.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.13 V (0.44%)477.9 V3.52 V (0.73%)295.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.69 V (0.35%)478.3 V2.79 V (0.58%)234.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.34 V (0.28%)478.7 V2.21 V (0.46%)185.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.06 V (0.22%)478.9 V1.75 V (0.37%)147.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.84 V (0.18%)479.2 V1.39 V (0.29%)116.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.71 V (0.15%)479.3 V1.18 V (0.25%)98.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.59 V (0.12%)479.4 V0.98 V (0.2%)82.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.51 V (0.11%)479.5 V0.84 V (0.18%)70.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.45 V (0.09%)479.6 V0.74 V (0.15%)61.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.36 V (0.07%)479.6 V0.59 V (0.12%)49.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.3 V (0.06%)479.7 V0.49 V (0.1%)41.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.24 V (0.05%)479.8 V0.39 V (0.08%)33.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (0.04%)479.8 V0.29 V (0.06%)24.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 100 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 4.27V (0.89%) and delivers 475.7V at the load.

What size aluminum wire is required for 80 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 4.43V (0.92%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.