🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 0.69%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 3.45V (0.72%)
Voltage at Load End476.7 VLoss: 3.33 V (720.9 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A67.89 V (14.14%)412.1 V111.99 V (23.33%)14699.6 WDrop/Amp High
12 AWG3.31 mm²20 A42.66 V (8.89%)437.3 V70.38 V (14.66%)9237.2 WDrop/Amp High
10 AWG5.26 mm²30 A26.85 V (5.59%)453.2 V44.29 V (9.23%)5812.8 WDrop/Amp High
8 AWG8.37 mm²50 A16.87 V (3.52%)463.1 V27.83 V (5.8%)3653.0 WDrop/Amp High
6 AWG13.3 mm²65 A10.62 V (2.21%)469.4 V17.51 V (3.65%)2298.9 WDrop/Amp High
4 AWG21.15 mm²85 A6.68 V (1.39%)473.3 V11.01 V (2.29%)1445.6 WDrop/Amp High
3 AWG26.67 mm²100 A5.3 V (1.1%)474.7 V8.73 V (1.82%)1146.4 WDrop/Amp High
2 AWG33.62 mm²115 A4.2 V (0.88%)475.8 V6.93 V (1.44%)909.4 WDrop/Amp High
1 AWG42.41 mm²130 A3.33 V (0.69%)476.7 V5.49 V (1.14%)720.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.64 V (0.55%)477.4 V4.35 V (0.91%)571.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.09 V (0.44%)477.9 V3.45 V (0.72%)453.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.66 V (0.35%)478.3 V2.74 V (0.57%)359.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.32 V (0.27%)478.7 V2.17 V (0.45%)285.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.11 V (0.23%)478.9 V1.84 V (0.38%)241.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.93 V (0.19%)479.1 V1.53 V (0.32%)201.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.8 V (0.17%)479.2 V1.31 V (0.27%)172.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.7 V (0.15%)479.3 V1.15 V (0.24%)150.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.56 V (0.12%)479.4 V0.92 V (0.19%)120.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.1%)479.5 V0.77 V (0.16%)100.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.37 V (0.08%)479.6 V0.61 V (0.13%)80.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.06%)479.7 V0.46 V (0.1%)60.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 100 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 3.33V (0.69%) and delivers 476.7V at the load.

What size aluminum wire is required for 125 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 3.45V (0.72%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.