🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 1.96%
Aluminum Wire (≤3% Drop)8 AWGDrop: 9.74V (2.03%)
Voltage at Load End470.6 VLoss: 9.4 V (406.9 W)
Power & Breaker (125%)20.78 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A23.76 V (4.95%)456.2 V39.2 V (8.17%)1029.0 WDrop/Amp High
12 AWG3.31 mm²20 A14.93 V (3.11%)465.1 V24.63 V (5.13%)646.6 WDrop/Amp High
10 AWG5.26 mm²30 A9.4 V (1.96%)470.6 V15.5 V (3.23%)406.9 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A5.91 V (1.23%)474.1 V9.74 V (2.03%)255.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.72 V (0.77%)476.3 V6.13 V (1.28%)160.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.34 V (0.49%)477.7 V3.85 V (0.8%)101.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.85 V (0.39%)478.1 V3.06 V (0.64%)80.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.47 V (0.31%)478.5 V2.43 V (0.51%)63.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.17 V (0.24%)478.8 V1.92 V (0.4%)50.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.92 V (0.19%)479.1 V1.52 V (0.32%)40.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.73 V (0.15%)479.3 V1.21 V (0.25%)31.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.58 V (0.12%)479.4 V0.96 V (0.2%)25.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.46 V (0.1%)479.5 V0.76 V (0.16%)20.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.39 V (0.08%)479.6 V0.64 V (0.13%)16.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.33 V (0.07%)479.7 V0.54 V (0.11%)14.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.28 V (0.06%)479.7 V0.46 V (0.1%)12.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.24 V (0.05%)479.8 V0.4 V (0.08%)10.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.2 V (0.04%)479.8 V0.32 V (0.07%)8.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.16 V (0.03%)479.8 V0.27 V (0.06%)7.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.03%)479.9 V0.21 V (0.04%)5.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.02%)479.9 V0.16 V (0.03%)4.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 175 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 9.4V (1.96%) and delivers 470.6V at the load.

What size aluminum wire is required for 25 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 9.74V (2.03%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.