🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 1000 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)18× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.98%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.62V (88.48%)
Voltage at Load End11.6 VLoss: 0.36 V (89.4 W)
Power & Breaker (125%)3.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 1000 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1567.96 V (13066.35%)0.0 V2586.4 V (21553.37%)391990.4 WDrop/Amp High
12 AWG3.31 mm²20 A985.31 V (8210.88%)0.0 V1625.29 V (13544.11%)246326.3 WDrop/Amp High
10 AWG5.26 mm²30 A620.03 V (5166.92%)0.0 V1022.76 V (8523.0%)155007.6 WDrop/Amp High
8 AWG8.37 mm²50 A389.65 V (3247.07%)0.0 V642.74 V (5356.15%)97412.2 WDrop/Amp High
6 AWG13.3 mm²65 A245.22 V (2043.46%)0.0 V404.49 V (3370.75%)61303.8 WDrop/Amp High
4 AWG21.15 mm²85 A154.2 V (1285.01%)0.0 V254.36 V (2119.67%)38550.4 WDrop/Amp High
3 AWG26.67 mm²100 A122.29 V (1019.05%)0.0 V201.71 V (1680.95%)30571.4 WDrop/Amp High
2 AWG33.62 mm²115 A97.01 V (808.39%)0.0 V160.02 V (1333.46%)24251.6 WDrop/Amp High
1 AWG42.41 mm²130 A76.9 V (640.84%)0.0 V126.85 V (1057.09%)19225.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A60.97 V (508.09%)0.0 V100.57 V (838.12%)15242.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A48.37 V (403.06%)0.0 V79.78 V (664.85%)12091.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A38.36 V (319.7%)0.0 V63.28 V (527.36%)9591.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A30.42 V (253.53%)0.0 V50.18 V (418.2%)7605.8 WDrop/Amp High
250 kcmil126.7 mm²255 A25.74 V (214.51%)0.0 V42.46 V (353.84%)6435.2 WDrop/Amp High
300 kcmil152.0 mm²285 A21.46 V (178.8%)0.0 V35.39 V (294.94%)5364.1 WDrop/Amp High
350 kcmil177.3 mm²310 A18.39 V (153.29%)0.0 V30.34 V (252.85%)4598.6 WDrop/Amp High
400 kcmil202.7 mm²335 A16.09 V (134.08%)0.0 V26.54 V (221.17%)4022.4 WDrop/Amp High
500 kcmil253.4 mm²380 A12.87 V (107.25%)0.0 V21.23 V (176.92%)3217.6 WDrop/Amp High
600 kcmil304.0 mm²420 A10.73 V (89.4%)1.3 V17.7 V (147.47%)2682.0 WDrop/Amp High
750 kcmil380.0 mm²475 A8.58 V (71.52%)3.4 V14.16 V (117.98%)2145.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.44 V (53.64%)5.6 V10.62 V (88.48%)1609.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 1000 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 1000 feet one-way at 12V (DC), you need 18× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.98%) and delivers 11.6V at the load.

What size aluminum wire is required for 250 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.62V (88.48%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.