⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.23%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.33V (11.06%)
Voltage at Load End11.7 VLoss: 0.27 V (67.0 W)
Power & Breaker (125%)3.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A196.0 V (1633.29%)0.0 V323.3 V (2694.17%)48998.8 WDrop/Amp High
12 AWG3.31 mm²20 A123.16 V (1026.36%)0.0 V203.16 V (1693.01%)30790.8 WDrop/Amp High
10 AWG5.26 mm²30 A77.5 V (645.87%)0.0 V127.85 V (1065.38%)19376.0 WDrop/Amp High
8 AWG8.37 mm²50 A48.71 V (405.88%)0.0 V80.34 V (669.52%)12176.5 WDrop/Amp High
6 AWG13.3 mm²65 A30.65 V (255.43%)0.0 V50.56 V (421.34%)7663.0 WDrop/Amp High
4 AWG21.15 mm²85 A19.28 V (160.63%)0.0 V31.8 V (264.96%)4818.8 WDrop/Amp High
3 AWG26.67 mm²100 A15.29 V (127.38%)0.0 V25.21 V (210.12%)3821.4 WDrop/Amp High
2 AWG33.62 mm²115 A12.13 V (101.05%)0.0 V20.0 V (166.68%)3031.5 WDrop/Amp High
1 AWG42.41 mm²130 A9.61 V (80.1%)2.4 V15.86 V (132.14%)2403.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.62 V (63.51%)4.4 V12.57 V (104.76%)1905.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.05 V (50.38%)6.0 V9.97 V (83.11%)1511.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.8 V (39.96%)7.2 V7.91 V (65.92%)1198.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.8 V (31.69%)8.2 V6.27 V (52.27%)950.7 WDrop/Amp High
250 kcmil126.7 mm²255 A3.22 V (26.81%)8.8 V5.31 V (44.23%)804.4 WDrop/Amp High
300 kcmil152.0 mm²285 A2.68 V (22.35%)9.3 V4.42 V (36.87%)670.5 WDrop/Amp High
350 kcmil177.3 mm²310 A2.3 V (19.16%)9.7 V3.79 V (31.61%)574.8 WDrop/Amp High
400 kcmil202.7 mm²335 A2.01 V (16.76%)10.0 V3.32 V (27.65%)502.8 WDrop/Amp High
500 kcmil253.4 mm²380 A1.61 V (13.41%)10.4 V2.65 V (22.11%)402.2 WDrop/Amp High
600 kcmil304.0 mm²420 A1.34 V (11.18%)10.7 V2.21 V (18.43%)335.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.07 V (8.94%)10.9 V1.77 V (14.75%)268.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.8 V (6.7%)11.2 V1.33 V (11.06%)201.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 125 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.27V (2.23%) and delivers 11.7V at the load.

What size aluminum wire is required for 250 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.33V (11.06%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.