🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.62V (4.42%)
Voltage at Load End233.6 VLoss: 6.44 V (1609.1 W)
Power & Breaker (125%)60.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1567.96 V (653.32%)0.0 V2586.4 V (1077.67%)391990.4 WDrop/Amp High
12 AWG3.31 mm²20 A985.31 V (410.54%)0.0 V1625.29 V (677.21%)246326.3 WDrop/Amp High
10 AWG5.26 mm²30 A620.03 V (258.35%)0.0 V1022.76 V (426.15%)155007.6 WDrop/Amp High
8 AWG8.37 mm²50 A389.65 V (162.35%)0.0 V642.74 V (267.81%)97412.2 WDrop/Amp High
6 AWG13.3 mm²65 A245.22 V (102.17%)0.0 V404.49 V (168.54%)61303.8 WDrop/Amp High
4 AWG21.15 mm²85 A154.2 V (64.25%)85.8 V254.36 V (105.98%)38550.4 WDrop/Amp High
3 AWG26.67 mm²100 A122.29 V (50.95%)117.7 V201.71 V (84.05%)30571.4 WDrop/Amp High
2 AWG33.62 mm²115 A97.01 V (40.42%)143.0 V160.02 V (66.67%)24251.6 WDrop/Amp High
1 AWG42.41 mm²130 A76.9 V (32.04%)163.1 V126.85 V (52.85%)19225.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A60.97 V (25.4%)179.0 V100.57 V (41.91%)15242.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A48.37 V (20.15%)191.6 V79.78 V (33.24%)12091.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A38.36 V (15.99%)201.6 V63.28 V (26.37%)9591.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A30.42 V (12.68%)209.6 V50.18 V (20.91%)7605.8 WDrop/Amp High
250 kcmil126.7 mm²255 A25.74 V (10.73%)214.3 V42.46 V (17.69%)6435.2 WDrop/Amp High
300 kcmil152.0 mm²285 A21.46 V (8.94%)218.5 V35.39 V (14.75%)5364.1 WDrop/Amp High
350 kcmil177.3 mm²310 A18.39 V (7.66%)221.6 V30.34 V (12.64%)4598.6 WDrop/Amp High
400 kcmil202.7 mm²335 A16.09 V (6.7%)223.9 V26.54 V (11.06%)4022.4 WDrop/Amp High
500 kcmil253.4 mm²380 A12.87 V (5.36%)227.1 V21.23 V (8.85%)3217.6 WDrop/Amp High
600 kcmil304.0 mm²420 A10.73 V (4.47%)229.3 V17.7 V (7.37%)2682.0 W~ ≤5%
750 kcmil380.0 mm²475 A8.58 V (3.58%)231.4 V14.16 V (5.9%)2145.6 W~ ≤5%
1000 kcmil506.7 mm²545 A6.44 V (2.68%)233.6 V10.62 V (4.42%)1609.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 1000 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 6.44V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 250 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.62V (4.42%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.