🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.88%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 5.31V (2.21%)
Voltage at Load End235.5 VLoss: 4.5 V (1126.2 W)
Power & Breaker (125%)60.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A274.39 V (114.33%)0.0 V452.62 V (188.59%)68598.3 WDrop/Amp High
12 AWG3.31 mm²20 A172.43 V (71.85%)67.6 V284.43 V (118.51%)43107.1 WDrop/Amp High
10 AWG5.26 mm²30 A108.51 V (45.21%)131.5 V178.98 V (74.58%)27126.3 WDrop/Amp High
8 AWG8.37 mm²50 A68.19 V (28.41%)171.8 V112.48 V (46.87%)17047.1 WDrop/Amp High
6 AWG13.3 mm²65 A42.91 V (17.88%)197.1 V70.79 V (29.49%)10728.2 WDrop/Amp High
4 AWG21.15 mm²85 A26.99 V (11.24%)213.0 V44.51 V (18.55%)6746.3 WDrop/Amp High
3 AWG26.67 mm²100 A21.4 V (8.92%)218.6 V35.3 V (14.71%)5350.0 WDrop/Amp High
2 AWG33.62 mm²115 A16.98 V (7.07%)223.0 V28.0 V (11.67%)4244.0 WDrop/Amp High
1 AWG42.41 mm²130 A13.46 V (5.61%)226.5 V22.2 V (9.25%)3364.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.67 V (4.45%)229.3 V17.6 V (7.33%)2667.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.46 V (3.53%)231.5 V13.96 V (5.82%)2116.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.71 V (2.8%)233.3 V11.07 V (4.61%)1678.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.32 V (2.22%)234.7 V8.78 V (3.66%)1331.0 WDrop/Amp High
250 kcmil126.7 mm²255 A4.5 V (1.88%)235.5 V7.43 V (3.1%)1126.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.75 V (1.56%)236.2 V6.19 V (2.58%)938.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.22 V (1.34%)236.8 V5.31 V (2.21%)804.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.82 V (1.17%)237.2 V4.64 V (1.94%)703.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.25 V (0.94%)237.7 V3.72 V (1.55%)563.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.88 V (0.78%)238.1 V3.1 V (1.29%)469.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.5 V (0.63%)238.5 V2.48 V (1.03%)375.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.13 V (0.47%)238.9 V1.86 V (0.77%)281.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 175 feet one-way at 240V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 4.5V (1.88%) and delivers 235.5V at the load.

What size aluminum wire is required for 250 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 5.31V (2.21%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.