🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.29%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 3.64V (1.52%)
Voltage at Load End236.9 VLoss: 3.09 V (772.2 W)
Power & Breaker (125%)60.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A188.16 V (78.4%)51.8 V310.37 V (129.32%)47038.8 WDrop/Amp High
12 AWG3.31 mm²20 A118.24 V (49.27%)121.8 V195.04 V (81.26%)29559.2 WDrop/Amp High
10 AWG5.26 mm²30 A74.4 V (31.0%)165.6 V122.73 V (51.14%)18600.9 WDrop/Amp High
8 AWG8.37 mm²50 A46.76 V (19.48%)193.2 V77.13 V (32.14%)11689.5 WDrop/Amp High
6 AWG13.3 mm²65 A29.43 V (12.26%)210.6 V48.54 V (20.22%)7356.5 WDrop/Amp High
4 AWG21.15 mm²85 A18.5 V (7.71%)221.5 V30.52 V (12.72%)4626.0 WDrop/Amp High
3 AWG26.67 mm²100 A14.67 V (6.11%)225.3 V24.21 V (10.09%)3668.6 WDrop/Amp High
2 AWG33.62 mm²115 A11.64 V (4.85%)228.4 V19.2 V (8.0%)2910.2 WDrop/Amp High
1 AWG42.41 mm²130 A9.23 V (3.85%)230.8 V15.22 V (6.34%)2307.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.32 V (3.05%)232.7 V12.07 V (5.03%)1829.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.8 V (2.42%)234.2 V9.57 V (3.99%)1451.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.6 V (1.92%)235.4 V7.59 V (3.16%)1150.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.65 V (1.52%)236.3 V6.02 V (2.51%)912.7 WDrop/Amp High
250 kcmil126.7 mm²255 A3.09 V (1.29%)236.9 V5.1 V (2.12%)772.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.57 V (1.07%)237.4 V4.25 V (1.77%)643.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.21 V (0.92%)237.8 V3.64 V (1.52%)551.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.93 V (0.8%)238.1 V3.18 V (1.33%)482.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.54 V (0.64%)238.5 V2.55 V (1.06%)386.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.29 V (0.54%)238.7 V2.12 V (0.88%)321.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.03 V (0.43%)239.0 V1.7 V (0.71%)257.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.77 V (0.32%)239.2 V1.27 V (0.53%)193.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 120 feet one-way at 240V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 3.09V (1.29%) and delivers 236.9V at the load.

What size aluminum wire is required for 250 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 3.64V (1.52%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.