⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 100 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.17V (9.73%)
Voltage at Load End11.7 VLoss: 0.35 V (97.3 W)
Power & Breaker (125%)3.3 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 100 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A172.48 V (1437.3%)0.0 V284.5 V (2370.87%)47430.8 WDrop/Amp High
12 AWG3.31 mm²20 A108.38 V (903.2%)0.0 V178.78 V (1489.85%)29805.5 WDrop/Amp High
10 AWG5.26 mm²30 A68.2 V (568.36%)0.0 V112.5 V (937.53%)18755.9 WDrop/Amp High
8 AWG8.37 mm²50 A42.86 V (357.18%)0.0 V70.7 V (589.18%)11786.9 WDrop/Amp High
6 AWG13.3 mm²65 A26.97 V (224.78%)0.0 V44.49 V (370.78%)7417.8 WDrop/Amp High
4 AWG21.15 mm²85 A16.96 V (141.35%)0.0 V27.98 V (233.16%)4664.6 WDrop/Amp High
3 AWG26.67 mm²100 A13.45 V (112.1%)0.0 V22.19 V (184.9%)3699.1 WDrop/Amp High
2 AWG33.62 mm²115 A10.67 V (88.92%)1.3 V17.6 V (146.68%)2934.4 WDrop/Amp High
1 AWG42.41 mm²130 A8.46 V (70.49%)3.5 V13.95 V (116.28%)2326.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.71 V (55.89%)5.3 V11.06 V (92.19%)1844.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.32 V (44.34%)6.7 V8.78 V (73.13%)1463.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.22 V (35.17%)7.8 V6.96 V (58.01%)1160.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.35 V (27.89%)8.7 V5.52 V (46.0%)920.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.83 V (23.6%)9.2 V4.67 V (38.92%)778.7 WDrop/Amp High
300 kcmil152.0 mm²285 A2.36 V (19.67%)9.6 V3.89 V (32.44%)649.1 WDrop/Amp High
350 kcmil177.3 mm²310 A2.02 V (16.86%)10.0 V3.34 V (27.81%)556.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.77 V (14.75%)10.2 V2.92 V (24.33%)486.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.42 V (11.8%)10.6 V2.34 V (19.46%)389.3 WDrop/Amp High
600 kcmil304.0 mm²420 A1.18 V (9.83%)10.8 V1.95 V (16.22%)324.5 WDrop/Amp High
750 kcmil380.0 mm²475 A0.94 V (7.87%)11.1 V1.56 V (12.98%)259.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.71 V (5.9%)11.3 V1.17 V (9.73%)194.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 100 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 100 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 275 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.17V (9.73%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.