🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.75V (14.6%)
Voltage at Load End11.7 VLoss: 0.35 V (97.4 W)
Power & Breaker (125%)3.3 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 150 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A258.71 V (2155.95%)0.0 V426.76 V (3556.31%)71146.3 WDrop/Amp High
12 AWG3.31 mm²20 A162.58 V (1354.79%)0.0 V268.17 V (2234.78%)44708.2 WDrop/Amp High
10 AWG5.26 mm²30 A102.31 V (852.54%)0.0 V168.76 V (1406.3%)28133.9 WDrop/Amp High
8 AWG8.37 mm²50 A64.29 V (535.77%)0.0 V106.05 V (883.77%)17680.3 WDrop/Amp High
6 AWG13.3 mm²65 A40.46 V (337.17%)0.0 V66.74 V (556.17%)11126.6 WDrop/Amp High
4 AWG21.15 mm²85 A25.44 V (212.03%)0.0 V41.97 V (349.75%)6996.9 WDrop/Amp High
3 AWG26.67 mm²100 A20.18 V (168.14%)0.0 V33.28 V (277.36%)5548.7 WDrop/Amp High
2 AWG33.62 mm²115 A16.01 V (133.38%)0.0 V26.4 V (220.02%)4401.7 WDrop/Amp High
1 AWG42.41 mm²130 A12.69 V (105.74%)0.0 V20.93 V (174.42%)3489.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.06 V (83.84%)1.9 V16.59 V (138.29%)2766.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.98 V (66.5%)4.0 V13.16 V (109.7%)2194.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.33 V (52.75%)5.7 V10.44 V (87.01%)1740.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.02 V (41.83%)7.0 V8.28 V (69.0%)1380.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.25 V (35.39%)7.8 V7.01 V (58.38%)1168.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.54 V (29.5%)8.5 V5.84 V (48.67%)973.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.04 V (25.29%)9.0 V5.01 V (41.72%)834.7 WDrop/Amp High
400 kcmil202.7 mm²335 A2.65 V (22.12%)9.3 V4.38 V (36.49%)730.1 WDrop/Amp High
500 kcmil253.4 mm²380 A2.12 V (17.7%)9.9 V3.5 V (29.19%)584.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.77 V (14.75%)10.2 V2.92 V (24.33%)486.8 WDrop/Amp High
750 kcmil380.0 mm²475 A1.42 V (11.8%)10.6 V2.34 V (19.47%)389.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.06 V (8.85%)10.9 V1.75 V (14.6%)292.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 150 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 150 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 275 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.75V (14.6%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.