🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.31V (2.6%)
Voltage at Load End11.6 VLoss: 0.35 V (97.3 W)
Power & Breaker (125%)3.3 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A34.5 V (287.46%)0.0 V56.9 V (474.17%)9486.2 WDrop/Amp High
12 AWG3.31 mm²20 A21.68 V (180.64%)0.0 V35.76 V (297.97%)5961.1 WDrop/Amp High
10 AWG5.26 mm²30 A13.64 V (113.67%)0.0 V22.5 V (187.51%)3751.2 WDrop/Amp High
8 AWG8.37 mm²50 A8.57 V (71.44%)3.4 V14.14 V (117.84%)2357.4 WDrop/Amp High
6 AWG13.3 mm²65 A5.39 V (44.96%)6.6 V8.9 V (74.16%)1483.6 WDrop/Amp High
4 AWG21.15 mm²85 A3.39 V (28.27%)8.6 V5.6 V (46.63%)932.9 WDrop/Amp High
3 AWG26.67 mm²100 A2.69 V (22.42%)9.3 V4.44 V (36.98%)739.8 WDrop/Amp High
2 AWG33.62 mm²115 A2.13 V (17.78%)9.9 V3.52 V (29.34%)586.9 WDrop/Amp High
1 AWG42.41 mm²130 A1.69 V (14.1%)10.3 V2.79 V (23.26%)465.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.34 V (11.18%)10.7 V2.21 V (18.44%)368.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.06 V (8.87%)10.9 V1.76 V (14.63%)292.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.84 V (7.03%)11.2 V1.39 V (11.6%)232.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.67 V (5.58%)11.3 V1.1 V (9.2%)184.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.57 V (4.72%)11.4 V0.93 V (7.78%)155.7 WDrop/Amp High
300 kcmil152.0 mm²285 A0.47 V (3.93%)11.5 V0.78 V (6.49%)129.8 W~ ≤5%
350 kcmil177.3 mm²310 A0.4 V (3.37%)11.6 V0.67 V (5.56%)111.3 W~ ≤5%
400 kcmil202.7 mm²335 A0.35 V (2.95%)11.6 V0.58 V (4.87%)97.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (2.36%)11.7 V0.47 V (3.89%)77.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.24 V (1.97%)11.8 V0.39 V (3.24%)64.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (1.57%)11.8 V0.31 V (2.6%)51.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (1.18%)11.9 V0.23 V (1.95%)38.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 20 feet one-way at 12V (DC), you need 400 kcmil copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.6V at the load.

What size aluminum wire is required for 275 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.31V (2.6%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.