🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.68V (4.87%)
Voltage at Load End232.9 VLoss: 7.08 V (1947.0 W)
Power & Breaker (125%)66.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1724.76 V (718.65%)0.0 V2845.04 V (1185.44%)474308.4 WDrop/Amp High
12 AWG3.31 mm²20 A1083.84 V (451.6%)0.0 V1787.82 V (744.93%)298054.8 WDrop/Amp High
10 AWG5.26 mm²30 A682.03 V (284.18%)0.0 V1125.04 V (468.77%)187559.2 WDrop/Amp High
8 AWG8.37 mm²50 A428.61 V (178.59%)0.0 V707.01 V (294.59%)117868.7 WDrop/Amp High
6 AWG13.3 mm²65 A269.74 V (112.39%)0.0 V444.94 V (185.39%)74177.5 WDrop/Amp High
4 AWG21.15 mm²85 A169.62 V (70.68%)70.4 V279.8 V (116.58%)46645.9 WDrop/Amp High
3 AWG26.67 mm²100 A134.51 V (56.05%)105.5 V221.89 V (92.45%)36991.4 WDrop/Amp High
2 AWG33.62 mm²115 A106.71 V (44.46%)133.3 V176.02 V (73.34%)29344.5 WDrop/Amp High
1 AWG42.41 mm²130 A84.59 V (35.25%)155.4 V139.54 V (58.14%)23262.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A67.07 V (27.95%)172.9 V110.63 V (46.1%)18443.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A53.2 V (22.17%)186.8 V87.76 V (36.57%)14630.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A42.2 V (17.58%)197.8 V69.61 V (29.0%)11605.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A33.47 V (13.94%)206.5 V55.2 V (23.0%)9203.0 WDrop/Amp High
250 kcmil126.7 mm²255 A28.31 V (11.8%)211.7 V46.71 V (19.46%)7786.6 WDrop/Amp High
300 kcmil152.0 mm²285 A23.6 V (9.83%)216.4 V38.93 V (16.22%)6490.5 WDrop/Amp High
350 kcmil177.3 mm²310 A20.23 V (8.43%)219.8 V33.38 V (13.91%)5564.4 WDrop/Amp High
400 kcmil202.7 mm²335 A17.7 V (7.37%)222.3 V29.19 V (12.16%)4867.1 WDrop/Amp High
500 kcmil253.4 mm²380 A14.16 V (5.9%)225.8 V23.35 V (9.73%)3893.3 WDrop/Amp High
600 kcmil304.0 mm²420 A11.8 V (4.92%)228.2 V19.47 V (8.11%)3245.3 W~ ≤5%
750 kcmil380.0 mm²475 A9.44 V (3.93%)230.6 V15.57 V (6.49%)2596.2 W~ ≤5%
1000 kcmil506.7 mm²545 A7.08 V (2.95%)232.9 V11.68 V (4.87%)1947.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 1000 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 7.08V (2.95%) and delivers 232.9V at the load.

What size aluminum wire is required for 275 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.68V (4.87%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.